6 - 1 6
Ultron DPM series
Standby
UPS-1.1
2019-Mar-01
09:30
UPS Setup
Parallel Setting
Parallel Group ID
Parallel ID
Common Battery
EVENT LOG
1
1
Enable
UPS-1.1
Parallel Group
ID No.
Parallel ID No.
WARNING:
The setup of each UPS’s '
Parallel Group ID
' (1 or 2) and '
Parallel ID
' (1
~ 8) through the LCD must be completed before start-up of the parallel
units. Otherwise, the parallel UPSs cannot be started. For other relevant
information, please refer to
7.9.6 Parallel Setting
.
3
For singe unit, turn
ON
the external maintenance bypass cabinet’s output breaker (Q4).
For parallel units, ensure that the output voltage difference between each parallel
UPS is below 5V. If larger than 5V, it is abnormal; please contact service personnel
immediately. If below 5V, turn
ON
each parallel UPS’s external maintenance bypass
cabinet’s output breaker (Q4).
4
(a) Single Input:
After the steps mentioned above is finished, it will be the bypass source to supply
power to the connected loads. Once the bypass start-up procedures are completed,
the following screen appears and the tri-color LED indicator remains yellow.
UPS-1.1
Bypass
2019-Mar-01
09:30
EVENT LOG
10 mins
Bypass
Load
0 %
Mains
Содержание Ultron DPM Series
Страница 12: ...1 6 Ultron DPM series 1 5 Standard Compliance UPS Capacity 1000kW 1250kW UL 1778...
Страница 38: ......
Страница 66: ......
Страница 232: ......
Страница 233: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 235: ...9 1 9 Maintenance Maintenance 9...
Страница 243: ...10 Troubleshooting 10 1 Troubleshooting 10...
Страница 256: ......
Страница 257: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Страница 260: ......
Страница 261: ...A2 1 Appendix 2 Warranty Warranty A2...
Страница 264: ......