6 - 3 9
6
UPS Operation
UPS-1.1
2019-Mar-01
09:30
EVENT LOG
Bypass
10 mins
Bypass
Load
0 %
Mains
5
Tap the Main Menu icon
located in the lower left corner of the LCD and select
UPS
Setup
ĺ
Mode Setting
ĺ
On-Line
. Next, the following screen appears.
Bypass
UPS-1.1
2019-Mar-01
09:30
UPS Setup
Mode Setting
EVENT LOG
Select to change
sys. mode
On-Line
ECO
Mode
Setting
6
After manually selecting
On-Line
mode via the LCD, tap the icon
located in the
upper left corner of the LCD to go back to the
Main Screen
.
7
(a) Single Input:
Switch
OFF
the external maintenance bypass cabinet’s input breaker (Q1). After
that, the grey inverter icon
will become green
and the UPS will begin
shutdown. About 3 ~ 5 minutes, the green inverter icon
becomes grey
DQGWKHWULFRORU/('LQGLFDWRUUHPDLQV\HOORZ3OHDVHVHHWKH¿JXUHEHORZ