9 Application Instructions API 150-199
DVP-PLC Application Manual
9-12
FEND
M1000
RTMU
K0
K10
RTMD
K0
IRET
I 001
M1000
M1000
RTMU
K1
K10
RTMD
K1
IRET
I 101
M1000
END
Both K0 should be the same
Both K1 should be the same
Remarks:
1.
We suggest you remove this instruction after you finish developing your PLC program.
2.
Due to the lower priority of the interruption enabled by RTMU, when RTMU is enabled, other high-speed pulse
input counting or high-speed pulse output may result in failure to trigger the timer.
3.
If you activate RTMU but do not activate RTMD before the end of the interruption, the interruption will not be
shut down.
4.
RTMU instruction activates 1 timer interruption in PLC. Therefore, if many RTMU or RTMD are executed at the
same time, confusion in the timer may occur. Please be aware of the situation.
Содержание DVP-PLC
Страница 1: ...PLC PLC...
Страница 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Страница 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Страница 250: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 38 X0 DIV D0 D10 D20 D0 D10 K4Y0 DIV...
Страница 270: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 58 RST M0 X0 RST T0 RST Y0 FMOV K0 D10 K5...
Страница 337: ...7 Application Instructions API 50 99 DVP PLC APPLICATION MANUAL 7 53 X10 STMR T10 K50 Y0 Y3 X10 Y1 Y2 5 sec 5 sec...
Страница 458: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 56 or relay itself See 2 3 for more information...
Страница 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Страница 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...