7 Application Instructions API 50-99
D V P - P L C A P P L I C AT I O N M A N U A L
7-6
b) When the present value in C249 changes from 99 to 100, the drive contact of C249 will be On immediately. When
the execution arrives at SET Y17, Y17 will still be affected by the scan time and will output after END instruction.
M1000
DCNT
C249
K100
SET
Y17
C249
DHSCS
K100
C249
Y10
On immediately
Program Example 3:
1. High speed counter interruption:
a) Operand
D
of DHSCS instruction can designate I0
□
0,
□
= 1 ~ 6, as the timing of interruption when the
counting reaches its target.
b) ES/EX/SS series MPU does not support high speed counter interruption.
c) SA/SX/SC series MPU supports high speed counter interruption. However, when DHSCS instruction
designates an I interruption, the designated high speed counter cannot be used in DHSCS, DHSCR, DHSZ
instructions. Misuse of high speed counter will result in error.
d) For SA/SX/SC series MPU, when the counting reaches the target, the interruption will occur. X0 is the
counter for counting input and the interruption No. is I010 (1 phase 2 inputs and A-B phase counter No. C246
~ C254 can only designate I010). X1 designates I020; X2 designates I030; X3 designates I040; X4
designates I050; X5 designates I060, totaling 6 points.
e) When the present value in C251 changes from 99 to 100 or 101 to 100, the program will jump to I010 and
execute the interruption service subroutine.
M1000
DCNT
C251
K1000
FEND
DHSCS
K100
C251
I010
M1000
Y1
IRET
END
I010
EI
2. In SA/SX/SC series MPU, M1059 is “I010 ~ I060 high speed counter interruption forbidden” flag.
3. In EH/EH2/SV series MPU, M1289 ~ M1294 are the respectively for I010 ~ I060 “high speed counter
interruption forbidden flags”, i.e. when M1294 = On, I060 interruption will be forbidden.
Interruption pointer I No. Interruption forbidden flag
Interruption pointer I No. Interruption forbidden flag
I010 M1289 I040 M1292
I020 M1290 I050 M1293
I030 M1291 I060 M1294
Содержание DVP-PLC
Страница 1: ...PLC PLC...
Страница 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Страница 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Страница 250: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 38 X0 DIV D0 D10 D20 D0 D10 K4Y0 DIV...
Страница 270: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 58 RST M0 X0 RST T0 RST Y0 FMOV K0 D10 K5...
Страница 337: ...7 Application Instructions API 50 99 DVP PLC APPLICATION MANUAL 7 53 X10 STMR T10 K50 Y0 Y3 X10 Y1 Y2 5 sec 5 sec...
Страница 458: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 56 or relay itself See 2 3 for more information...
Страница 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Страница 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...