6 Application Instructions API 00-49
DVP-PLC Application Manual
6-25
Program Example 3:
To avoid coincidence of the device numbers to be moved designated by the two operands and cause confusion,
please be aware of the arrangement on the designated device numbers.
1. When
S
>
D
, the instruction is processed following the order
1
→
2
→
3
X10
BMOV
D20
D19
K3
D19
D20
D21
D20
D21
D22
2
1
3
2.
In EH/EH2/SV, when
S
<
D
, the instruction is processed following the order
1
→
2
→
3
D11
D13
X11
BMOV
D10
D11
K3
D10
D11
D12
1
3
2
3.
In ESEX/SS/SA/SX/SC, when
S
<
D
, avoid the number difference of “1” and the instruction is processed
following the order
3
→
2
→
1
. If the devices have the number difference of “1”, the contents in D11 ~ D13 will all
be the content in D10.
D11
D13
X11
BMOV
D10
D11
K3
D10
D11
D12
1
3
2
Содержание DVP-PLC
Страница 1: ...PLC PLC...
Страница 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Страница 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Страница 250: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 38 X0 DIV D0 D10 D20 D0 D10 K4Y0 DIV...
Страница 270: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 58 RST M0 X0 RST T0 RST Y0 FMOV K0 D10 K5...
Страница 337: ...7 Application Instructions API 50 99 DVP PLC APPLICATION MANUAL 7 53 X10 STMR T10 K50 Y0 Y3 X10 Y1 Y2 5 sec 5 sec...
Страница 458: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 56 or relay itself See 2 3 for more information...
Страница 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Страница 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...