9 Application Instructions API 150-199
DVP-PLC Application Manual
9-35
6.
Wiring of DVP-EH series PLC and a Mitsubishi MR-J2-
□
A Servo drive:
L
N
X0
X1
X2
X3
X4
X5
X6
S/S
+24V
200KPPS
R
S
T
U
V
W
24V
24G
X7
X10
X11
X12
X13
X14
X15
X16
X17
Y6
Y7
C4
Y4
Y0
Y1
C2
C0
C1
DOG
JOG(+)
JOG(-)
CN1B
VDD
COM
D01
ZSP
TLC
ALM
RES
LSP
LSN
EMG
TL
SON
SG
ABSR
ABSM
CN1A
OP
INP
RD
LG
SG
CR
SG
PP
SG
NP
SG
10
2
10
3
20
8
20
1
19
18
14
8
9
10
5
9
15
17
16
14
18
6
19
4
13
3
ABS bit 0
ABS bit 1
CN2
DVP32EH00T
EH MPU
Mitsubishi servo drive
MR-J2 series
220VAC
Single phase
3-
p
h
ase
po
we
r
ABS transmission
Stop
Left limit
Right limit
Zero return
Forward
positioning
Reverse
positioning
Positioning completed
Preparation completed
Z-phase signal (zero point)
Read ABS ready
Enter ABS mode
S
e
rv
o
m
o
to
r
Error
counter
Electric
gear
Encoder
Clear pulse
Pulse output
Forward/backward direction
Note:
(a) When detecting an absolute position by using DABSR instruction, the parameter setting of a Mitsubishi
MR-J2-
□
A servo drive that connects to Delta EH series PLC:
P0: position mode.
P1: using absolute value.
P21: pulse input type as Pulse+DIR.
(b) The forward/reverse limit switch should be connected to SERVO AMP.
(c) When using OP (Z-phase signal) in servo and given that the Z-phase signal is a high-frequency one when
the motor is running at high speed, the valid detection can only be possible when the signal is within the
range detectable by PLC. When using OP (Z phase signal) of the servo, if Z phase signal is a high
frequency signal during high-speed motor operation, the high frequency signal shall be within the available
range that can be detected by PLC.
7.
Cautions when designing a position control program:
a) There is no limitation on the times of using the position control instructions, API 156 ZRN, API 157 PLSV,
API 158 DRVI, and API 159 DRVA. However, the user still have to note that:
Содержание DVP-PLC
Страница 1: ...PLC PLC...
Страница 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Страница 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Страница 250: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 38 X0 DIV D0 D10 D20 D0 D10 K4Y0 DIV...
Страница 270: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 58 RST M0 X0 RST T0 RST Y0 FMOV K0 D10 K5...
Страница 337: ...7 Application Instructions API 50 99 DVP PLC APPLICATION MANUAL 7 53 X10 STMR T10 K50 Y0 Y3 X10 Y1 Y2 5 sec 5 sec...
Страница 458: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 56 or relay itself See 2 3 for more information...
Страница 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Страница 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...