2 Functions of Devices in DVP-PLC
DVP-PLC Application Manual
2-106
a) Using Y10 pulse output
Mode 1 – Planned deceleration
Applicable to: DDRVI and DDRVA instructions
Criteria for executing planned deceleration: Shut down the criteria contact for pulse output instruction and
turn “Off” M1334.
The time from executing planned deceleration to the end of pulse output: The time set in D1343 (for
acceleration/deceleration)
The solid lines in the figure below are the originally planned routes and the dotted lines refer to the routes
after planned deceleration is executed.
Frequency
Target frequency
Start frequency
D1340
Instruction shut down and M1334 = Off
Time
Acceleration/deceleration time
D1343
Mode 2 – Output shutdown
Applicable to: DDRVI, DDRVA, PLSY instructions
Criteria for executing output shutdown: Shut down the criteria contact for pulse output instruction and turn
“On” M1334.(Because PLSY does not have acceleration/deceleration setting, M1334 does not need to
be set in PLSY)
The time from executing output shutdown to the end of pulse output: Max. 1 scan cycle.
The solid lines in the figure below are the originally planned routes and the dotted lines refer to the routes
after output shutdown is executed.
Frequency
Target frequency
Start frequency
D1340
Instruction shut down and M1334 = On
Time
Mode 3 – Immediate output shutdown
Applicable to: DDRVI, DDRVA, PLSY instructions
Criteria for executing immediate output shutdown: M1310 = On (set before executing the instruction) and
the criteria triggers set in X10 (D1166 = K0 refers to rising-edge; D1166 = K1 refers to falling-edge)
The time from executing immediate output shutdown to the end of pulse output: Max. 1 pulse time.
The solid lines in the figure below are the originally planned routes and the dotted lines refer to the
routes after X10 is triggered.
Содержание DVP-PLC
Страница 1: ...PLC PLC...
Страница 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Страница 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Страница 250: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 38 X0 DIV D0 D10 D20 D0 D10 K4Y0 DIV...
Страница 270: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 58 RST M0 X0 RST T0 RST Y0 FMOV K0 D10 K5...
Страница 337: ...7 Application Instructions API 50 99 DVP PLC APPLICATION MANUAL 7 53 X10 STMR T10 K50 Y0 Y3 X10 Y1 Y2 5 sec 5 sec...
Страница 458: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 56 or relay itself See 2 3 for more information...
Страница 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Страница 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...