8 Application Instructions API 100-149
DVP-PLC Application Manual
8-40
API
Mnemonic Operands
Function
128
D POW P
Floating Point Power Operation
Controllers
ES/EX/SS SA/SX/SC EH/SV
Bit Devices
Word Devices
Program Steps
Type
OP
X Y M S K H
KnX
KnY KnM KnS T
C
D
E
F
S
1
*
*
*
S
2
*
*
*
D
*
DPOW, DPOWP: 13 steps
PULSE 16-bit 32-bit
ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV
Operands:
S
1
: Device for base.
S
2
: Device for exponent.
D
: Device for operation result
Explanations:
1. See the specifications of each model for their range of use.
2. This instruction performs power multiplication of binary floating point
S
1
and
S
2
and stores the result in
D
.
D
=
POW
[
S
1
+ 1,
S
1
]
^
[
S
2
+ 1,
S
2
]
3. Only positives are valid for the content in
S
1
. Both positives and negatives are valid for the content in
S
2
. When
designating
D
registers, the data should be 32-bit and the operation should be performed in floating point
system. Therefore,
S
1
and
S
2
should be converted into floating point values.
Example: When
S
1
S2
=
D
,
D
= ?
Assume
S
1
= 5,
S
2
= 3,
D
= 5
3
=125
4. If the absolute value of the result
>
maximum floating point available, the carry flag M1022 = On.
5. If the absolute value of the result
<
minimum floating point available, the borrow flag M1021 = On.
6. If the result = 0, the zero flag M1020 = On.
Program Example:
1. When M0 = On, convert (D1, D0) and (D3, D2) into binary floating points and store them in the 32-bit registers
(D11, D10) and (D13, D12).
2. When M1= On, perform POW operation on the binary floting points in 32-bit registers (D11, D10) and (D13,
D12) and store the result in the 32-bit register (D21, D20).
3. When M2 = On, convert the binary floating point (D21, D20) into decimal floating point (D30
× 10
[D31]
)
and store
it in register (D31, D30).
M0
RST
M1081
M1
D10
D12
M2
DEBCD
D20
D30
D2
D12
D20
DFLT
DFLT
DPOW
D0
D10
Remarks:
Содержание DVP-PLC
Страница 1: ...PLC PLC...
Страница 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Страница 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Страница 250: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 38 X0 DIV D0 D10 D20 D0 D10 K4Y0 DIV...
Страница 270: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 58 RST M0 X0 RST T0 RST Y0 FMOV K0 D10 K5...
Страница 337: ...7 Application Instructions API 50 99 DVP PLC APPLICATION MANUAL 7 53 X10 STMR T10 K50 Y0 Y3 X10 Y1 Y2 5 sec 5 sec...
Страница 458: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 56 or relay itself See 2 3 for more information...
Страница 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Страница 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...