7 Application Instructions API 50-99
D V P - P L C A P P L I C AT I O N M A N U A L
7-77
CR #10
CR #9
Lower 16-bit
Designated CR number
Higher 16-bit
d) Number of groups “n” to be transmitted: n = 2 in 16-bit instructions and n = 1 in 32-bit instructions mean
the same.
D0
D1
D2
D3
D4
D5
CR #5
CR #6
CR #7
CR #8
CR #9
CR #10
D0
D1
D2
D3
D4
D5
CR #5
CR #6
CR #7
CR #8
CR #9
CR #10
Designated device
Designated CR
Designated device Designated CR
16-bit instruction when n=6
32-bit instruction when n=3
4. ES/EX/SS series MPU does not have M1083. During the execution of FROM/TO instruction, all external or
internal interruption subroutines will be forbidden. The interruptions are allowed only after FROM/TO instruction
finishes its execution. FROM/TO instruction can also be used in an interruption subroutine.
5. M1083 for switching instruction modes in SA/SX/SC/EH/EH2/SV series MPU:
a) When M1083 = Off, during the execution of FROM/TO instruction, all external or internal interruption
subroutines will be forbidden. The interruptions are allowed only after FROM/TO instruction finishes its
execution. FROM/TO instruction can also be used in an interruption subroutine.
b) When M1083 = On and an interruption signal occurs during the execution of FROM/TO instruction, the
interruption will be processed first (with a 100us delay) and the execution of FROM/TO will be stopped. After
the interruption subroutine finishes its execution, the program will jump to the next instructio of FROM/TO.
FROM/TO cannot be used in an interruption subroutine.
FROM/TO Application Example 1:
Adjust the A/D conversion curve of DVP-04AD. Set the OFFSET value of CH1 as 0V (= K0
LSB
) and GAIN value as
2.5V (= K2,000
LSB
).
M1002
TO
K0
K1
H0
K1
TO
K0
K33
H0
K1
X0
TO
K0
K18
K0
K1
TO
K0
K24
K2000
K1
1. Write H0 to CR#1 of anlog input module No. 0 and set CH1 as mode 0 (voltage input: -10V ~ +10V).
2. Write H0 to CR#33 and allow OFFSET/GAIN tuning in CH1 ~ CH4.
3. When X0 goes from Off to On, write the OFFSET value K0
LSB
into CR#18 and the GAIN value K2,000
LSB
into
Содержание DVP-PLC
Страница 1: ...PLC PLC...
Страница 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Страница 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Страница 250: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 38 X0 DIV D0 D10 D20 D0 D10 K4Y0 DIV...
Страница 270: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 58 RST M0 X0 RST T0 RST Y0 FMOV K0 D10 K5...
Страница 337: ...7 Application Instructions API 50 99 DVP PLC APPLICATION MANUAL 7 53 X10 STMR T10 K50 Y0 Y3 X10 Y1 Y2 5 sec 5 sec...
Страница 458: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 56 or relay itself See 2 3 for more information...
Страница 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Страница 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...