9 Application Instructions API 150-199
DVP-PLC Application Manual
9-18
100KHz will be output by 100KHz. The default setting in SC series MPU is 100Hz.
Note: During the control of the stepping motor, please consider the resonance and the
limitation on the start frequency when you set up the speed.
D1341, D1342
:
(For EH/EH2/SV series MPU) For setting up the maximum speed when the position control
instructions (API 156 ZRN, API 158 DRVI, API 159 DRVA) are being executed. D1342 is for
high word; D1341 is for low word.
Range of setting: 200KHz fixed.
D1343 (D1353)
:
For setting up the time of the first acceleration segment and the last deceleration segment
when the position control instructions (API 156 ZRN, API 158 DRVI, API 159 DRVA) are
executing CH0 (CH1) outputs.
Range of setting:
For EH/EH2/SV series MPU, the acceleration/deceleration time has to be longer than 10ms.
The time shorter than 10ms or longer than 10,000ms will be output by 10ms. The default
setting in EH/EH2/SV series MPU is 100ms. For SC series MPU, the time has to be 50 ~
20,000ms. The time shorter than 50ms will be regarded as 50ms.
Note: During the control of the stepping motor, please consider the resonance and the
limitation on the start frequency when you set up the speed.
D1348, D1349
:
(For SC series MPU) Registers for the first group (Y0, Y1) output pulse present value of
position control instructions (API 156 ZRN, API 158 DRVI, API 159 DRVA). The present
value increases or decreases according to the corresponding rotation direction. D1349 is for
high word; D1348 is for low word.
D1350, D1351
:
(For SC series MPU) Registers for the second group (Y11) output pulse present value of
position control instructions (API 156 ZRN, API 158 DRVI, API 159 DRVA). The present
value increases or decreases according to the corresponding rotation direction. D1351 is for
high word; D1350 is for low word.
Содержание DVP-PLC
Страница 1: ...PLC PLC...
Страница 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Страница 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Страница 250: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 38 X0 DIV D0 D10 D20 D0 D10 K4Y0 DIV...
Страница 270: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 58 RST M0 X0 RST T0 RST Y0 FMOV K0 D10 K5...
Страница 337: ...7 Application Instructions API 50 99 DVP PLC APPLICATION MANUAL 7 53 X10 STMR T10 K50 Y0 Y3 X10 Y1 Y2 5 sec 5 sec...
Страница 458: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 56 or relay itself See 2 3 for more information...
Страница 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Страница 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...