7 Application Instructions API 50-99
D V P - P L C A P P L I C AT I O N M A N U A L
7-63
Remarks:
1. When this instruction is being executed, it will require 8 scans to obtain one valid keyed-in value. A scan period
that is too long or too short may result in poor keyed-in effect, which can be avoided by the following methods:
a) If the scan period is too short, I/O may not be able to respond in time, resulting in not being able to read the
keyed-in value correctly. In this case, please fix the scan time.
b) If the scan period is too long, the key may respond slowly. In this case, write this instruction into the time
interruption subroutine to fix the time for the execution of this instruction.
2. Functions
of
M1167:
a)
When M1167 = On, HKY instruction will be able to input the hexadecimal value of 0 ~ F.
b)
When M1167 = Off, HKY instruction will see A ~ F as function keys.
3. Functions of D1037 (only supports EH/EH2/SV series MPU):
Write D1037 to set the overlapping time for keys (unit: ms). The overlapping time will vary upon different program
scan time and the settings in D1037.
Содержание DVP-PLC
Страница 1: ...PLC PLC...
Страница 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Страница 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Страница 250: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 38 X0 DIV D0 D10 D20 D0 D10 K4Y0 DIV...
Страница 270: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 58 RST M0 X0 RST T0 RST Y0 FMOV K0 D10 K5...
Страница 337: ...7 Application Instructions API 50 99 DVP PLC APPLICATION MANUAL 7 53 X10 STMR T10 K50 Y0 Y3 X10 Y1 Y2 5 sec 5 sec...
Страница 458: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 56 or relay itself See 2 3 for more information...
Страница 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Страница 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...