9 Application Instructions API 150-199
DVP-PLC Application Manual
9-24
API Mnemonic
Operands
Function
158
D DRVI
Drive to Increment
Controllers
ES/EX/SS SA/SX/SC EH/SV
Bit Devices
Word Devices
Program Steps
Type
OP
X Y M S K H
KnX
KnY KnM KnS T
C
D
E
F
S
1
*
*
*
*
*
*
*
*
*
*
*
S
2
*
*
*
*
*
*
*
*
*
*
*
D
1
*
D
2
*
*
*
DRVI: 9 steps
DDRVI: 17 steps
PULSE 16-bit 32-bit
ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV
Operands:
S
1
: Number of output pulses (relative designation)
S
2
: Pulse output frequency
D
1
: Pulse output device (please
use transistor output module)
D
2
: Output device for the signal of rotation direction
Explanations:
1.
See remarks for the setting range of
S
1
,
S
2
,
D
1
and
D
2
.
2.
S
1
and
S
2
of SC series MPU only support device K, H and D.
3.
Flag: see remarks for more details.
4.
S
1
is the number of output pulses (relative designation). For EH/EH2/SV series MPU, the 16-bit instruction can
designate the range -32,768 ~ +32,767. The range designated by 32-bit instruction is -2,147,483,648 ~
+2,147,483,647. For SC series MPU, the 32-bit instruction can designate the range -2,147,483,648 ~
+2,147,483,647. “+/-” signs indicate forward/backward directions.
5.
S
2
is the designated pulse output frequency. For EH/EH2/SV series MPU, the 16-bit instruction can designate
its range 10 ~ 32,767Hz. The range designated by 32-bit instruction is 10 ~ 200,000Hz. For SC series MPU,
the 32-bit instruction can designate the range 100 ~ 100,000Hz.
6.
EH series MPU has two groups of A/B phase pulse output, CH0 (Y0, Y1) and CH1 (Y2, Y3). EH2/SV series
MPU has four groups of A/B phase pulse output, CH0 (Y0, Y1), CH1 (Y2, Y3), CH2 (Y4, Y5) and CH3 (Y6, Y7).
See remarks for the setup methods.
7.
Pulse output device
D
1
in different models
Model
SC MPU
EH MPU
EH2/SV MPU
Pulse output end
Y10, Y11
Y0, Y2
Y0, Y2, Y4, Y6
8.
The operation of
D
2
corresponds to the “+” or “-“ of
S
1
. When
S
1
is “+”,
D
2
will be On; when
S
1
is “-“,
D
2
will be
Off.
D
2
will not be Off immediately after the pulse output is over; it will be Off only when the drive contact of the
instruction turns Off.
9.
For EH/EH2/SV series MPU,
S
1
is
- The 32-bit data stored in the present value registers D1337 (high word) and D1336 (low word) of CH0 (Y0,
Y1).
- The 32-bit data stored in the present value registers D1339 (high word) and D1338 (low word) of CH1 (Y2,
Y3).
- The 32-bit data stored in the present value registers D1376 (high word) and D1375 (low word) of CH2 (Y4,
Y5).
- The 32-bit data stored in the present value registers D1378 (high word) and D1377 (low word) of CH3 (Y5,
Содержание DVP-PLC
Страница 1: ...PLC PLC...
Страница 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Страница 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Страница 250: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 38 X0 DIV D0 D10 D20 D0 D10 K4Y0 DIV...
Страница 270: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 58 RST M0 X0 RST T0 RST Y0 FMOV K0 D10 K5...
Страница 337: ...7 Application Instructions API 50 99 DVP PLC APPLICATION MANUAL 7 53 X10 STMR T10 K50 Y0 Y3 X10 Y1 Y2 5 sec 5 sec...
Страница 458: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 56 or relay itself See 2 3 for more information...
Страница 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Страница 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...