7 Application Instructions API 50-99
D V P - P L C A P P L I C AT I O N M A N U A L
7-103
API Mnemonic Operands
Function
85
VRRD
P
Volume Read
Controllers
ES/EX/SS SA/SX/SC EH/SV
Bit Devices
Word Devices
Program Steps
Type
OP
X Y M S K H
KnX KnY KnM KnS T
C
D
E
F
S
*
*
D
*
*
*
*
*
*
*
*
VRRD, VRRDP: 5 steps
PULSE 16-bit 32-bit
ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV
Operands:
S
: No. of VR
D
: Device for storing the volume of VR
Explanations:
1. Range
of
S
: 0 ~ 7; without function card: 0 ~ 1.
2. See the specifications of each model for their range of use.
3. Flags: M1178, M1179. See remarks for more details.
4. VRRD instruction is used for reading 2 points (No.0, No.1) of PLC or the VR rotary switch volume change in the 6
points of the function cards (No.2 ~ No.7) and converting the data into values 0 ~ 255 (stored in
D
).
5. If you are to set up the timer by the VR volume, simply rotate the VR to modify the set time in the timer. If you are
to acquire a value larger than 255, multiply
D
by a constant.
Program Example 1:
1. When X0 = On, VR0 volume changed will be converted into an 8-bit BIN value (0 ~ 255) and stored in D0.
2. When X1 = On, the imer T0 will start to time with the content in D0 as the set value in the timer.
X1
TMR
T0
D0
X0
VRRD
K0
D0
Program Example 2:
1. Read the VR volume in order: The VR0 ~ VR7 rotary switches on the PLC correspond to
S
= K0 ~ K7 of VRRD
instruction. E index register modification is used in the example below, K0E = K0 ~ K7.
2. The timer converts the scale 0 ~ 10 on the rotary switch into 0 ~ 255. The timing unit of T0 ~ T7 is 0.1 second;
therefore, the set time in the timer will be 0 ~ 25.5 seconds.
M1000
RST
E
F OR
K8
M1000
VRRD
INC
E
D100E
NEXT
K 0E
Содержание DVP-PLC
Страница 1: ...PLC PLC...
Страница 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Страница 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Страница 250: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 38 X0 DIV D0 D10 D20 D0 D10 K4Y0 DIV...
Страница 270: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 58 RST M0 X0 RST T0 RST Y0 FMOV K0 D10 K5...
Страница 337: ...7 Application Instructions API 50 99 DVP PLC APPLICATION MANUAL 7 53 X10 STMR T10 K50 Y0 Y3 X10 Y1 Y2 5 sec 5 sec...
Страница 458: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 56 or relay itself See 2 3 for more information...
Страница 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Страница 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...