7 Application Instructions API 50-99
D V P - P L C A P P L I C AT I O N M A N U A L
7-28
1
2
3
200
0.5ms
1ms
Y0 output
Remarks:
1. Flags and special registers for ES/EX/SS series MPU:
M1010: When On, Y0 output will be continuous with no limitation on the number of pulses. When Off, the
number of output pulses from Y0 will be decided by
S
2
.
M1023: When On, Y1 output will be continuous with no limitation on the number of pulses. When Off, the
number of output pulses from Y1 will be decided by
S
2
.
M1029: On when Y0 pulse output is completed.
M1030: On when Y1 pulse output is completed.
M1078: Y0 output pauses.
M1079: Y1 output pauses.
D1030: Low word of the current number of output pulses from Y0
D1031: High word of the current number of output pulses from Y0
D1032: Low word of the current number of output pulses from Y1
D1033: High word of the current number of output pulses from Y1
2. Flags and special registers for SA/SX/SC series MPU:
M1010: (SA/SX/SC) When On, Y0 output will be continuous with no limitation on the number of pulses.
When Off, the number of output pulses from Y0 will be decided by
S
2
.
M1023: (SA/SX/SC) When On, Y1 output will be continuous with no limitation on the number of pulses.
When Off, the number of output pulses from Y1 will be decided by
S
2
.
M1029: (SA/SX/SC) On when Y0 pulse output is completed.
M1030: (SA/SX/SC) On when Y1 pulse output is completed.
M1078: (SA/SX/SC) Y0 output pauses.
M1079: (SA/SX/SC) Y1 output pauses.
M1102: (SC) On when Y10 pulse output is completed.
M1103: (SC) On when Y11 pulse output is completed.
D1030: (SA/SX/SC) Low word of the current number of output pulses from Y0
D1031: (SA/SX/SC) High word of the current number of output pulses from Y0
D1032: (SA/SX/SC) Low word of the current number of output pulses from Y1
D1033: (SA/SX/SC) High word of the current number of output pulses from Y1
D1348: (SC) Low word of the current number of output pulses from Y10
D1349: (SC) High word of the current number of output pulses from Y10
D1350: (SC) Low word of the current number of output pulses from Y11
D1351: (SC) High word of the current number of output pulses from Y11
Содержание DVP-PLC
Страница 1: ...PLC PLC...
Страница 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Страница 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Страница 250: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 38 X0 DIV D0 D10 D20 D0 D10 K4Y0 DIV...
Страница 270: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 58 RST M0 X0 RST T0 RST Y0 FMOV K0 D10 K5...
Страница 337: ...7 Application Instructions API 50 99 DVP PLC APPLICATION MANUAL 7 53 X10 STMR T10 K50 Y0 Y3 X10 Y1 Y2 5 sec 5 sec...
Страница 458: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 56 or relay itself See 2 3 for more information...
Страница 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Страница 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...