8 Application Instructions API 100-149
DVP-PLC Application Manual
8-62
Example 3:
To speed up the speed to reach the target temperature, we correct the sampling time as 4 seconds
(D12 = K40, D30 = K4,000). The results are shown in the diagram below.
From the diagram below, we see that the overall control time has been shortened as 37 minutes. Therefore, we
find out that modifying the sampling time can speed up the time for reaching the target temperature.
Example 4:
To see if we can reach the target temperature faster, we modify the sampling time frim example 3
into 2 seconds (D12 = K20, D30 = K2,000). The results are shown in the diagram below.
From the diagram below, we see that the sampling time that is too short will cause the control system to become
too sensitive and lead to up and down fluctuations.
Содержание DVP-PLC
Страница 1: ...PLC PLC...
Страница 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Страница 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Страница 250: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 38 X0 DIV D0 D10 D20 D0 D10 K4Y0 DIV...
Страница 270: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 58 RST M0 X0 RST T0 RST Y0 FMOV K0 D10 K5...
Страница 337: ...7 Application Instructions API 50 99 DVP PLC APPLICATION MANUAL 7 53 X10 STMR T10 K50 Y0 Y3 X10 Y1 Y2 5 sec 5 sec...
Страница 458: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 56 or relay itself See 2 3 for more information...
Страница 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Страница 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...