2 Functions of Devices in DVP-PLC
DVP-PLC Application Manual
2-73
M1017
±30 seconds
correction
From “Off” to “On”, the correction is enabled.
0 ~ 29 second: minute intact; second reset to 0
30~ 59 second: 1; second reset to 0
M1076
RTC malfunction
Set value exceeds the range; dead battery
M1082
Flag change on RTC On: Modification on RTC
D1313
Second
0 ~ 59
D1314
Minute
0 ~ 59
D1315
Hour
0 ~ 23
D1316
Day
1 ~ 31
D1317
Month
1 ~ 12
D1318
Week
1 ~ 7
D1319
Year
0 ~ 99 (last 2 digits of Year in A.D.)
2.
If the set value in RTC is incorrect, the time will be recovered as “Saturday, 00:00 Jan. 1, 2000” when PLC is
powered and restarted.
3.
D1313 ~ D1319 will immediately update the RTC only when in TRD instruction or WPLSoft monitoring mode.
4.
How to make corrections on RTC:
a) Use TWR instruction fir SA/SX/SX/EH/EH2/SV series MPU. See API 167 TWR for more details.
b) Use WPLSoft or digital display panel DU-01.
Function Group
π
(PI)
Number
D1018, D1019
Contents:
1.
D1018 and D1019 are combined as 32-bit data register for storing the floating point value of
π
(PI)
2.
loating point value = H 40490FDB
Function Group
Adjustment on Input Terminal Response Time
Number
D1020, D1021
Contents:
1.
D1020 can be used for setting up the response time of receiving pulses at X0 ~X7 for SS/ES/EX/SA/SX/SC
series MPU. (Setup range: 0 ~ 20; Unit: ms)
2.
D1021 can be used for setting up the response time of receiving pulses at X10 ~X17 for ES series MPU. (Setup
range: 0 ~ 20; Unit: ms)
3.
D1021 can be used for setting up the response time of receiving pulses at X10 ~X11 for SC series MPU. (Setup
range: 0 ~ 1,000; Unit: time)
4.
D1020 can be used for setting up the response time of receiving pulses at X0 ~X7 for EH/EH2/SV series MPU.
(Setup range: 0 ~ 60; Unit: ms)
Содержание DVP-PLC
Страница 1: ...PLC PLC...
Страница 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Страница 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Страница 250: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 38 X0 DIV D0 D10 D20 D0 D10 K4Y0 DIV...
Страница 270: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 58 RST M0 X0 RST T0 RST Y0 FMOV K0 D10 K5...
Страница 337: ...7 Application Instructions API 50 99 DVP PLC APPLICATION MANUAL 7 53 X10 STMR T10 K50 Y0 Y3 X10 Y1 Y2 5 sec 5 sec...
Страница 458: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 56 or relay itself See 2 3 for more information...
Страница 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Страница 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...