2 Functions of Devices in DVP-PLC
DVP-PLC Application Manual
2-27
2-phase AB input high-speed counter
Example:
LD
X10
RST C251
LD X11
DCNT C251
K5
LD C251
OUT Y0
C251
Y0
X11
C251
K5
DCNT
C251
RST
X10
1.
When X10 is On, RST instsruction will be executed. The PV in C251 will be cleared to “0” and the output contact
will be reset to be Off.
2.
In C251, when X11 is On and C251 receives the A-phase signals from X0 and B-phase signals from X1, the PV
in the counter will count up (plus 1) or count down (minus 1). You can select different counting modes if you use
EH/EH2/SV series MPU.
3.
When the counting of C251 reaches SV K5, the contact of C251 will be On. If there are still input signals coming
in, the counting will continue.
4.
The counting modes (normal frequency, double frequency or 4 times frequency) of C251 (HHSC0) in ES/SA
series MPU can be set up by D1022. The default setting is double frequency mode.
5.
C251 in EH/EH2/SV series MPU has external input signals to reset X2 and start X3.
6.
The counting modes (normal frequency, double frequency, triple frequency or 4 times frequency) of C251
(HHSC0) in EH/EH2/SV series MPU can be set up by D1225. The default setting is double frequency mode.
7.
The external input contact of reset signal of C246 (HHSC0) in EH/EH2/SV series MPU is disabled by M1264.
The external input contact of start signal is disabled by M1265.
8.
The internal input contact of reset signal of C246 (HHSC0) in EH/EH2/SV series MPU is disabled by M1272.
The internal input contact of start signal is disabled by M1273.
ES/EX/SS and SA/SX/SC series MPU (double frequency)
0
1
2
3
4
5
X11
X10
6
3
0
1
2
3
4
5
A-phase X0
B-phase X1
PV in C251
Contact Y0, C251
Counting up
Counting down
EH/EH2/SV series MPU (double frequency)
Содержание DVP-PLC
Страница 1: ...PLC PLC...
Страница 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Страница 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Страница 250: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 38 X0 DIV D0 D10 D20 D0 D10 K4Y0 DIV...
Страница 270: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 58 RST M0 X0 RST T0 RST Y0 FMOV K0 D10 K5...
Страница 337: ...7 Application Instructions API 50 99 DVP PLC APPLICATION MANUAL 7 53 X10 STMR T10 K50 Y0 Y3 X10 Y1 Y2 5 sec 5 sec...
Страница 458: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 56 or relay itself See 2 3 for more information...
Страница 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Страница 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...