7 Application Instructions API 50-99
D V P - P L C A P P L I C AT I O N M A N U A L
7-13
f) Special registers for relevant flags and settings of high speed counters:
Flag
Function
M1150
DHSZ instruction in multiple set values comparison mode
M1151
The execution of DHSZ multiple set values comparison mode is completed.
M1152
Set DHSZ instruction as frequency control mode
M1153
DHSZ frequency control mode has been executed.
M1235 ~ M1245
Designating the counting direction of high speed counters C235 ~ C245
When M12
□□
= Off, C2
□□
will perform a counting up.
When M12
□□
= On, C2
□□
will perform a counting down.
M1246 ~ M1255
Monitor the counting direction of high speed counters C246 ~ C255
When M12
□□
= Off, C2
□□
will perform a counting up.
When M12
□□
= On, C2
□□
will perform a counting down.
M1260
X5 as the reset input signal of all high speed counters
M1261
High-speed comparison flag for DHSCR instruction
M1264
Disable the external control signal input point of HHSC0 reset signal point (R)
M1265
Disable the external control signal input point of HHSC0 start signal point (S)
M1266
Disable the external control signal input point of HHSC1 reset signal point (R)
M1267
Disable the external control signal input point of HHSC1 start signal point (S)
M1268
Disable the external control signal input point of HHSC2 reset signal point (R)
M1269
Disable the external control signal input point of HHSC2 start signal point (S)
M1270
Disable the external control signal input point of HHSC3 reset signal point (R)
M1271
Disable the external control signal input point of HHSC3 start signal point (S)
M1272
Internal control signal input point of HHSC0 reset signal point (R)
M1273
Internal control signal input point of HHSC0 start signal point (S)
M1274
Internal control signal input point of HHSC1 reset signal point (R)
M1275
Internal control signal input point of HHSC1 start signal point (S)
M1276
Internal control signal input point of HHSC2 reset signal point (R)
M1277
Internal control signal input point of HHSC2 start signal point (S)
M1278
Internal control signal input point of HHSC3 reset signal point (R)
M1279
Internal control signal input point of HHSC3 start signal point (S)
M1289
High speed counter I010 interruption forbidden
M1290
High speed counter I020 interruption forbidden
M1291
High speed counter I030 interruption forbidden
M1292
High speed counter I040 interruption forbidden
M1293
High speed counter I050 interruption forbidden
M1294
High speed counter I060 interruption forbidden
M1312
C235 Start input point control
M1313
C236 Start input point control
Содержание DVP-PLC
Страница 1: ...PLC PLC...
Страница 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Страница 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Страница 250: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 38 X0 DIV D0 D10 D20 D0 D10 K4Y0 DIV...
Страница 270: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 58 RST M0 X0 RST T0 RST Y0 FMOV K0 D10 K5...
Страница 337: ...7 Application Instructions API 50 99 DVP PLC APPLICATION MANUAL 7 53 X10 STMR T10 K50 Y0 Y3 X10 Y1 Y2 5 sec 5 sec...
Страница 458: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 56 or relay itself See 2 3 for more information...
Страница 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Страница 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...