7 Application Instructions API 50-99
D V P - P L C A P P L I C AT I O N M A N U A L
7-37
Output: Y0 or Y2
Pulse speed (Hz)
Targeted speed: 10 ~ 200,000Hz
Time(Sec)
Decel time
below 5,000ms
Accel time
below 5,000ms
16-bit command:110~32,767PLS
32-bit command:110~2,147,483,647PLS
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10 10
10-step
variations
10-step
variations
Time interval among
pulse outputs
=
x
1/10
S
3
Every speed variation
=
x
1/10
S
1
S
2
( )
S
3
( )
S
3
Remarks:
1.
The outputs cannot be the same as those of API 57 PLSY and API 58 PWM.
2.
When there are many high speed pulse output instructions (PLSY, PWM, PLSR) in a program for Y0 output, and
provided these instructions are being executed in the same scan period, PLC will set up and output the
instructions with the fewest steps.
3.
With M1133 ~ M1135 and D1133, Y0 of SA/SX/SC series MPU can output pulses at up to 50KHz. See 2.11 for
more details of special D and special M.
Range of output frequecies for all series:
MPU
ES/EX/SS
SA/SX/SC
EH
EH2/SV
Range
Y0: 10 ~ 10,000Hz
Y1: 10 ~ 10,000Hz
Y0: 10 ~ 30,000Hz
Y1: 10 ~ 30,000Hz
Y0: 10 ~ 200,000Hz
Y2: 10 ~ 200,000Hz
Y0: 10 ~ 200,000Hz
Y2: 10 ~ 200,000Hz
Y4: 10 ~ 200,000Hz
Y6: 10 ~ 200,000Hz
Functions in EH series MPU:
1.
Relevant devices for EH/EH2/SV series MPU:
X0
PLSR
K1000
D10
K3000
Y0
2.
The range of pulse speed for this instruction is 10 ~ 200,000Hz. If the set values of maximum speed and
acceleration/deceleration time exceed the range, PLC will operate by the default value that is within the range.
Operand
S
1
S
2
S
3
D
Explanation
Max. frequency
Total number of pulses
Accel/Decel time
Output point
16-bit
10 ~ 32,767Hz
110 ~ 32,767
Range
32-bit
10 ~ 200KHz
110 ~ 2,147,483,647
1 ~ 5,000ms
Y0 ~ Y7
Definition
K0: No output
Kn: Designated
frequency
Kn: Designated
number
Flag: M1067, M1068
See settings of D1220,
D1221
Содержание DVP-PLC
Страница 1: ...PLC PLC...
Страница 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Страница 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Страница 250: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 38 X0 DIV D0 D10 D20 D0 D10 K4Y0 DIV...
Страница 270: ...6 Application Instructions API 00 49 DVP PLC Application Manual 6 58 RST M0 X0 RST T0 RST Y0 FMOV K0 D10 K5...
Страница 337: ...7 Application Instructions API 50 99 DVP PLC APPLICATION MANUAL 7 53 X10 STMR T10 K50 Y0 Y3 X10 Y1 Y2 5 sec 5 sec...
Страница 458: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 56 or relay itself See 2 3 for more information...
Страница 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Страница 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...