PNU
Parameter
Factory setting
Range
Changes 4-Setup
Conver-
sion
Data
#
description
during operation
index
type
200
Output frequency range
0 - 120 Hz
0 - 1000 Hz
No
Yes
0
5
201
Output frequency low limit, f
MIN
0.0 Hz
0.0 - f
MAX
Yes
Yes
-1
6
202
Output frequency high limit, f
MAX
50 Hz
f
MIN
- par. 200
Yes
Yes
-1
6
203
Reference site
Hand/Auto linked reference
Yes
Yes
0
5
204
Minimum reference, Ref
MIN
0.000
0.000-par. 100
Yes
Yes
-3
4
205
Maximum reference, Ref
MAX
50.000
par. 100-999.999,999
Yes
Yes
-3
4
206
Ramp-up time
Depends on the unit
1 - 3600
Yes
Yes
0
7
207
Ramp-down time
Depends on the unit
1 - 3600
Yes
Yes
0
7
208
Automatic ramp-up/down
Enable
Yes
Yes
0
5
209
Jog frequency
10.0 Hz
0.0 - par. 100
Yes
Yes
-1
6
210
Reference type
Sum
Yes
Yes
0
5
211
Preset reference 1
0.00 %
-100.00 - 100.00 %
Yes
Yes
-2
3
212
Preset reference 2
0.00 %
-100.00 - 100.00 %
Yes
Yes
-2
3
213
Preset reference 3
0.00 %
-100.00 - 100.00 %
Yes
Yes
-2
3
214
Preset reference 4
0.00 %
-100.00 - 100.00 %
Yes
Yes
-2
3
215
Current limit, l
LIM
1.0 x l
VLT,N[A]
0,1-1,1 x l
VLT,N[A]
Yes
Yes
-1
6
216
Frequency bypass, bandwidth
0 Hz
0 - 100 Hz
Yes
Yes
0
6
217
Frequency bypass 1
120 Hz
0.0 - par.200
Yes
Yes
-1
6
218
Frequency bypass 2
120 Hz
0.0 - par.200
Yes
Yes
-1
6
219
Frequency bypass 3
120 Hz
0.0 - par.200
Yes
Yes
-1
6
220
Frequency bypass 4
120 Hz
0.0 - par.200
Yes
Yes
-1
6
221
Warning: Low current, l
LOW
0.0 A
0.0 - par.222
Yes
Yes
-1
6
222
Warning: High current, l
HIGH
l
VLT,MAX
Par.221 - l
VLT,MAX
Yes
Yes
-1
6
223
Warning: Low frequency, f
LOW
0.0 Hz
0.0 - par.224
Yes
Yes
-1
6
224
Warning: High frequency, f
HIGH
120.0 Hz
Par.223 - par.200/202
Yes
Yes
-1
6
225
Warning: Low reference, Ref
LOW
-999,999.999
-999,999.999 - par.226
Yes
Yes
-3
4
226
Warning: High reference, Ref
HIGH
999,999.999
Par.225 - 999,999.999
Yes
Yes
-3
4
227
Warning: Low feedback, FB
LOW
-999,999.999
-999,999.999 - par.228
Yes
Yes
-3
4
228
Warning: High feedback, FB
HIGH
999,999.999
Par. 227 - 999,999.999
Yes
Yes
-3
4
Changes during operation:
"Yes" means that the parameter can be changed,
while the frequency converter is in operation. "No"
means that the frequency converter must be stopped
before a change can be made.
4-Setup:
"Yes" means that the parameter can be programmed
individually in each of the four setups, i.e. the same
parameter can have four different data values. "No"
means that the data value will be the same in all four
setups.
Conversion index:
This number refers to a conversion figure to be used
when writing or reading by means of a frequency con-
verter.
Conversion index
Conversion factor
74
0.1
2
100
1
10
0
1
-1
0.1
-2
0.01
-3
0.001
-4
0.0001
Data type:
Data type shows the type and length of the telegram.
Data type
Description
3
Integer 16
4
Integer 32
5
Unsigned 8
6
Unsigned 16
7
Unsigned 32
9
Text string
VLT
®
6000 HVAC Series
212
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark
Содержание VLT 6000 HVAC Series
Страница 31: ...Ordering form VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 31 Introduction to HVAC ...
Страница 63: ...Mechanical dimensions VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 63 Installation ...
Страница 75: ...VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 75 Installation ...
Страница 204: ...VLT 6000 HVAC Series 204 MG 61 B5 02 VLT is a registered Danfoss trademark ...