Automatic motor adaptation has ben completed. The
frequency converter is now ready for operation after
the
Reset
signal has been enabled. Please note that
the motor will start after the frequency converter has
received the
Reset
signal.
Stand by (STANDBY)
The frequency converter is able to start the motor
when a start command is received.
Stop (STOP)
The motor has been stopped via a stop signal from a
digital input, [OFF/STOP]-buttom or serial communi-
cation.
DC stop (DC STOP)
The DC brake in parameter 114-116 has been ena-
bled.
DRIVE ready (UN. READY)
The frequency converter is ready for operation, but
terminal 27 is a logic “0” and/or a
Coasting command
has been received via the serial communication.
Not ready (NOT READY)
The frequency converter is not ready for operation,
because of a trip or because OFF1, OFF2 or OFF3 is
a logic ‘0’.
Start disabled (START IN.)
This status will only be displayed if, in parameter
599
Statemachine, Profidrive
[1] has been selected
and OFF2 or OFF3 is a logic ‘0’.
Exceptions XXXX (EXCEPTIONS XXXX)
The microprocessor of the control card has stopped
and the frequency converter is out of operation.
The cause may be noise on the mains, motor or control
cables, leading to a stop of the control card microproc-
essor.
Check for EMC-correct connection of these cables.
VLT
®
6000 HVAC Series
186
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark
Содержание VLT 6000 HVAC Series
Страница 31: ...Ordering form VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 31 Introduction to HVAC ...
Страница 63: ...Mechanical dimensions VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 63 Installation ...
Страница 75: ...VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 75 Installation ...
Страница 204: ...VLT 6000 HVAC Series 204 MG 61 B5 02 VLT is a registered Danfoss trademark ...