Technical data, mains supply 3x380-460V
According to international requirements
VLT type 6052
6062
6072
6102
6122
Output current
I
VLT,N
[A] (380-440 V) 73.0
90.0
106
147
177
I
VLT, MAX
(60 s) [A]
(380-440 V)
80.3
99.0
117
162
195
I
VLT,N
[A] (441-460 V)
65.0 77.0
106
130
160
I
VLT, MAX
(60 s) [A]
(441-460 V)
71.5 84.7
117
143
176
Output power
S
VLT,N
[kVA] (400 V) 52.5
64.7
73.4
102
123
S
VLT,N
[kVA] (460 V)
51.8 61.3
84.5
104
127
Typical shaft output
P
VLT,N
[kW] 37
45
55
75
90
Typical shaft output
P
VLT,N
[HP] 50
60
75
100
125
Max. cable cross-section
to motor and DC-bus, IP
20
[mm
2
]/[AWG]
2) 4) 6)
35/2
50/0
50/0
120 / 250
mcm
5)
120 / 250
mcm
5)
Max. cable cross-section
to motor and DC-bus, IP
54
35/2
50/0 50/0
150 / 300
mcm
5)
150 / 300
mcm
5)
Min. cable cross-section
to motor and DC-bus
[mm
2
]/[AWG]
2) 4)
10/8 16/6
16/6
25/4
25/4
Max. input current
I
L,N
[A] (380 V) 72.0
89.0
104
145
174
(RMS)
I
L,N
[A] (460 V)
64.0 77.0
104
128
158
Max. cable cross-section
power, IP 20
[mm
2
]/[AWG]
2) 4) 6)
35/2 50/0
50/0
120 / 250
mcm
120 / 250
mcm
Max. cable cross-section
power, IP 54
35/2
50/0 50/0
150 / 300
mcm
150 / 300
mcm
Max. pre-fuses
[-]/UL
1)
[A] 100/100
125/125 150/150 225/225 250/250
Efficiency at rated frequency
0.96
0.96 0.96
0.98
0.98
Weight IP 20
[kg] 41
42
43
54
54
Weight IP 54
[kg]
56 56
60
77
77
Power loss at max. load.
[W] 1275
1571
1322
1467
1766
Enclosure
IP 20/IP 54
1. For type of fuse, see section
Fuses
.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals.
Max. cable cross section is the maximum possible cable cross section that can be fitted on the
terminals.
Always comply with national and local regulations on min. cable cross-section.
5. DC connection 95 mm
2
/AWG 3/0.
6. Aluminium cables with cross-section above 35 mm
2
must be connected by use of an Al-Cu con-
nector.
VLT
®
6000 HVAC Series
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark
51
In
s
ta
lla
ti
on
Содержание VLT 6000 HVAC Series
Страница 31: ...Ordering form VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 31 Introduction to HVAC ...
Страница 63: ...Mechanical dimensions VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 63 Installation ...
Страница 75: ...VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 75 Installation ...
Страница 204: ...VLT 6000 HVAC Series 204 MG 61 B5 02 VLT is a registered Danfoss trademark ...