No.
Description
Warning
Alarm
Trip locked
1
10 Volts low (10 VOLT LOW)
x
2
Live zero fault (LIVE ZERO ERROR)
x
x
4
Mains imbalance (MAINS IMBALANCE)
x
x
x
5
Voltage warning high (DC LINK VOLTAGE HIGH)
x
6
Voltage warning low (DC LINK VOLTAGE LOW)
x
7
Overvoltage (DC LINK OVERVOLT)
x
x
8
Undervoltage (DC LINK UNDERVOLT)
x
x
9
Inverter overloaded (INVERTER TIME)
x
x
10
Motor overloaded (MOTOR TIME)
x
x
11
Motor thermistor (MOTOR THERMISTOR)
x
x
12
Current limit (CURRENT LIMIT)
x
x
13
Overcurrent (OVERCURRENT)
x
x
x
14
Earth fault (EARTH FAULT)
x
x
15
Switch mode fault (SWITCH MODE FAULT)
x
x
16
Short-circuit (CURR.SHORT CIRCUIT)
x
x
17
Serial communication timeout (STD BUSTIMEOUT)
x
x
18
HPFB bus timeout (HPFB TIMEOUT)
x
x
19
Fault in EEprom on power card (EE ERROR POWER)
x
20
Fault in EEprom on control card (EE ERROR CONTROL)
x
22
Auto-optimisation not OK (AMA FAULT)
x
29
Heat-sink temperature too high (HEAT SINK OVERTEMP.)
x
30
Motor phase U missing (MISSING MOT.PHASE U)
x
31
Motor phase V missing (MISSING MOT.PHASE V)
x
32
Motor phase W missing (MISSING MOT.PHASE W)
x
34
HPFB communication fault (HPFB COMM. FAULT)
x
x
37
Inverter fault (GATE DRIVE FAULT)
x
x
39
Check parameters 104 and 106 (CHECK P.104 & P.106)
x
40
Check parameters 103 and 105 (CHECK P.103 & P.106)
x
41
Motor too big (MOTOR TOO BIG)
x
42
Motor too small (MOTOR TOO SMALL)
x
60
Safety stop (EXTERNAL FAULT)
x
61
Output frequency low (FOUT < FLOW)
x
62
Output frequency high (FOUT > FHIGH)
x
63
Output current low (I MOTOR < I LOW)
x
x
64
Output current high (I MOTOR > I HIGH)
x
65
Feedback low (FEEDBACK < FDB LOW)
x
66
Feedback high (FEEDBACK > FDB HIGH)
x
67
Reference low (REF. < REF. LOW)
x
68
Reference high (REF. > REF. HIGH)
x
69
Temperature auto derate (TEMP.AUTO DERATE)
x
80
Fire mode was active (FIRE MODE WAS ACTIVE)
x
x
81
RTC not ready (RTC NOT READY)
x
99
Unknown fault (UNKNOWN ALARM)
x
x
VLT
®
6000 HVAC Series
188
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark
Содержание VLT 6000 HVAC Series
Страница 31: ...Ordering form VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 31 Introduction to HVAC ...
Страница 63: ...Mechanical dimensions VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 63 Installation ...
Страница 75: ...VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 75 Installation ...
Страница 204: ...VLT 6000 HVAC Series 204 MG 61 B5 02 VLT is a registered Danfoss trademark ...