Activation/deactivation can be programmed in param-
eter 324
Relay 1, ON delay
and parameter 325
Relay 1,
OFF delay
.
See
General technical data
.
Description of choice:
See data choice and connections in
Relay outputs.
324
Relay 01, ON delay
(RELAY1 ON DELAY)
Value:
0 - 600 sec.
0 sec.
Function:
This parameter allows a delay of the cut-in time of relay
1 (terminals 1-2).
Description of choice:
Enter the desired value.
325
Relay 01, OFF delay
(RELAY1 OFF DELAY)
Value:
0 - 600 sec.
0 sec.
Function:
This parameter makes it possible to delay the cut-out
time of relay 01 (terminals 1-2).
Description of choice:
Enter the desired value.
326
Relay 2, output function
(RELAY2 FUNCTION)
Value:
See functions of relay 2 on previous page.
Function:
This output activates a relay switch. Relay switch 2 can
be used for indicating status and warnings. The relay
is activated when the conditions for the relevant data
values have been fulfilled.
See
General technical data
.
Description of choice:
See data choice and connections in
Relay outputs.
327
Pulse reference, max. frequency
(PULSE REF. MAX)
Value:
100 - 65000 Hz at terminal 29
5000 Hz
100 - 5000 Hz at terminal 17
Function:
This parameter is used to set the pulse value that must
correspond to the maximum reference, parameter 205
Maximum reference, Ref
MAX
.
The pulse reference signal can be connected via ter-
minal 17 or 29.
Description of choice:
Set the required maximum pulse reference.
328
Pulse feedback, max. frequency
(PULSE FDBK MAX.)
Value:
100 - 65000 Hz at terminal 33
25000 Hz
Function:
This is where the pulse value that must correspond to
the maximum feedback value is set. The pulse fedback
signal is connected via terminal 33.
Description of choice:
Set the desired feedback value.
364
Terminal 42, bus control
(CONTROL OUTPUT 42)
365
Terminal 45, bus control
(CONTROL OUTPUT 45)
Value:
VLT
®
6000 HVAC Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark
137
Pr
ogr
a
mmi
ng
Содержание VLT 6000 HVAC Series
Страница 31: ...Ordering form VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 31 Introduction to HVAC ...
Страница 63: ...Mechanical dimensions VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 63 Installation ...
Страница 75: ...VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 75 Installation ...
Страница 204: ...VLT 6000 HVAC Series 204 MG 61 B5 02 VLT is a registered Danfoss trademark ...