Description of choice:
The table below shows when the motor is running and
is coasting when
Digital input
[0],
Serial communica-
tion
[1],
Logic and
[2] or
Logic or
[3] has been selected.
NB!
Please note that terminal 27 and bit 03 of
the control word are active in the case of
logic '0'.
Digital input
[0]
Serial communication
[1]
Serial
Serial
Kl. 27
com
.
Function
Kl. 27
com
.
Function
0
0
Coasting
0
0
Coasting
0
1
Coasting
0
1
Motor run.
1
0
Motor run.
1
0
Coasting
1
1
Motor run.
1
1
Motor run.
Logic and
[2]
Logic or
[3]
Serial
Serial
Kl. 27
com
.
Function
Kl. 27
com
.
Function
0
0
Coasting
0
0
Coasting
0
1
Motor run.
0
1
Coasting
1
0
Motor run.
1
0
Coasting
1
1
Motor run.
1
1
Motor run.
504
DC brake
(DC BRAKE)
Value:
Digital input (DIGITAL INPUT)
[0]
Serial communication (SERIAL PORT)
[1]
Logic and (LOGIC AND)
[2]
Logic or (LOGIC OR)
[3]
Function:
See functional description under parameter 503
Coasting
.
Description of choice:
The table below shows when the motor is running and
is DC-braking when
Digital input
[0],
Serial communi-
cation
[1],
Logic and
[2] or
Logic or
[3] has been selec-
ted.
NB!
Please note that
DC braking inverse
[3] via
terminal 19, terminal 27 and bit 03 of the
control word is active in the case of logic
'0'.
Digital input
[0]
Serial communication
[1]
Serial
Serial
Term.
19/27
co
m.
Function
Term.
19/27
co
m.
Function
0
0
DC-brake
0
0
DC-brake
0
1
DC-brake
0
1
Motor run.
1
0
Motor run.
1
0
DC-brake
1
1
Motor run.
1
1
Motor run.
Logic and
[2]
Logic or
[3]
Serial
Serial
Term.
19/27
co
m.
Function
Term.
19/27
co
m.
Function
0
0
DC-brake
0
0
DC-brake
0
1
Motor run.
0
1
DC-brake
1
0
Motor run.
1
0
DC-brake
1
1
Motor run.
1
1
Motor run.
505
Start
(START)
Value:
Digital input (DIGITAL INPUT)
[0]
Serial communication (SERIAL PORT)
[1]
Logic and (LOGIC AND)
[2]
Logic or (LOGIC OR)
[3]
Function:
See functional description under parameter 503
Coasting
.
Description of choice:
The table below shows when the motor has stopped
and gives the situations in which the frequency con-
verter has a start command when
Digital input
[0],
Serial communication
[1],
Logic and
[2] or
Logic or
[3]
has been selected.
Digital input
[0]
Serial communication
[1]
Serial
Serial
Kl.18
com
.
Function
Kl.18
com
.
Function
0
0
Stop
0
0
Stop
0
1
Stop
0
1
Start
1
0
Start
1
0
Stop
1
1
Start
1
1
Start
Logic and
[2]
Logic or
[3]
Serial
Serial
Kl.18
com
.
Function
Kl.18
com
.
Function
0
0
Stop
0
0
Stop
0
1
Stop
0
1
Start
1
0
Stop
1
0
Start
1
1
Start
1
1
Start
VLT
®
6000 HVAC Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark
167
Pr
ogr
a
mmi
ng
Содержание VLT 6000 HVAC Series
Страница 31: ...Ordering form VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 31 Introduction to HVAC ...
Страница 63: ...Mechanical dimensions VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 63 Installation ...
Страница 75: ...VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 75 Installation ...
Страница 204: ...VLT 6000 HVAC Series 204 MG 61 B5 02 VLT is a registered Danfoss trademark ...