Extended status word, warning word, and alarm
word
Extended status word, warning word, and alarm word
are shown in Hex format on the display. If there is more
than one warning or alarm, a sum of the total warnings
or alarms will be shown.
The descriptions relating to the extended status word
can be seen in Status word as per FC protocol, and
the descriptions can also be read out via the serial bus
in parameter 531,
Warning word
, 532,
Extended status
word
and 529,
Alarm word
.
Hex code
Extended status word
00000001
Overvoltage control active
00000002
Start delay
00000004
Sleep boost active
00000008
Sleep mode active
00000010
Automatic motor adaptation completed
00000020
Automatic motor adaptation running
00000040
Reversing and start
00000080
Ramp operation
00000100
Reversing
00000200
Speed = reference
00000400
Running
00000800
Local ref. = 1,
Remote controlled ref. = 0
00001000
OFF mode = 1
00002000
Auto mode = 0, Hand mode = 1
00004000
Start blocked
00008000
Start blocked signal missing
00010000
Freeze output
00020000
Freeze output blocked
00040000
Jogging
00080000
Jog blocked
00100000
Stand by
00200000
Stop
00400000
DC stop
00800000
Drive ready
01000000
Relay 123 active
02000000
Drive ready
04000000
Control ready
08000000
Start prevented
10000000
Profibus OFF3 active
20000000
Profibus OFF2 active
40000000
Profibus OFF1 active
80000000
Reserved
Hex code
Warning word
00000001
Reference high
00000002
Fault in EEprom on control card
00000004
Fault in EEprom on power card
00000008
HPFB bus timeout
00000010
Serial communication timeout
00000020
Overcurrent
00000040
Current limit
00000080
Motor thermistor
00000100
Motor overtemperature
00000200
Inverter overtemperature
00000400
Undervoltage
00000800
Overvoltage
00001000
Overvoltage
00002000
Voltage warning high
00004000
Mains imbalance
00008000
Live zero fault
00010000
Under 10 Volt (terminal 50)
00020000
Reference low
00040000
Feedback high
00080000
Feedback low
00100000
Output current high
00200000
Reserved
00400000
Profibus communication fault
00800000
Output current low
01000000
Output frequency high
02000000
Output frequency low
04000000
AMA - motor too small
08000000
AMA - motor too big
10000000
AMA - check par. 102, 103, 105
20000000
AMA - check par. 102, 104, 106
40000000
Reserved
80000000
Warning word set in w. word 2.
Hex code
Warning word 2
00000001
Fire mode limits exceeded
00000002
Fire mode active
00000004
Fire mode bypass
00000008
RTC not ready
VLT
®
6000 HVAC Series
174
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark
Содержание VLT 6000 HVAC Series
Страница 31: ...Ordering form VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 31 Introduction to HVAC ...
Страница 63: ...Mechanical dimensions VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 63 Installation ...
Страница 75: ...VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 75 Installation ...
Страница 204: ...VLT 6000 HVAC Series 204 MG 61 B5 02 VLT is a registered Danfoss trademark ...