List of warnings and alarms
The table gives the different warnings and alarms and
indicates whether the fault locks the frequency con-
verter. After Trip locked, the mains supply must be cut
and the fault must be corrected. Reconnect the mains
supply and reset the frequency converter before being
ready. A Trip can be reset manually in three ways
1.
Via the control key [RESET]
2.
Via a digital input
3.
Via serial communication In addition, an au-
tomatic reset may be selected in parameter
400
Reset function.
Wherever a cross is placed under both Warning and
Alarm, this can mean that a warning precedes the
alarm. It can also mean that it is possible to program
whether a given fault is to result in a warning or an
alarm. This is possible, e.g. in parameter 117
Motor
thermal protection
. After a trip, the motor will be coast-
ing and on the frequency converter alarm and warning
will flash. If the fault is removed, only the alarm will
flash. After a reset, the frequency converter will be
ready to start operation again.
VLT
®
6000 HVAC Series
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark
187
A
ll
ab
out VL
T
60
00
HV
AC
Содержание VLT 6000 HVAC Series
Страница 31: ...Ordering form VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 31 Introduction to HVAC ...
Страница 63: ...Mechanical dimensions VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 63 Installation ...
Страница 75: ...VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 75 Installation ...
Страница 204: ...VLT 6000 HVAC Series 204 MG 61 B5 02 VLT is a registered Danfoss trademark ...