015
Reset on LCP
(RESET BUTTON)
Value:
Disable (DISABLE)
[0]
Enable (ENABLE)
[1]
Function:
This parameter allows selection/deselection of the re-
set key on the control panel.
Description of choice:
If
Disable
[0] is selected in this parameter, the [RESET]
key will be inactive.
NB!
Only select
Disable
[0] if an external reset
signal has been connected via the digital
inputs.
016
Lock for data change
(DATA CHANGE LOCK)
Value:
Not locked (NOT LOCKED)
[0]
Locked (LOCKED)
[1]
Function:
This parameter allows the control panel to be “locked”,
which means that it is not possible to carry out data
modifications via the control unit.
Description of choice:
If
Locked
[1] is selected, data modifications in the pa-
rameters cannot be made, although it will still be pos-
sible to carry out data modifications via the bus.
Parameters 007-010
Display readout
can be changed
via the control panel.
It is also possible to lock for data modifications in these
parameters by means of a digital input, see parame-
ters 300-307
Digital inputs
.
017
Operating state at power up, local con-
trol
(POWER UP ACTION)
Value:
Auto restart (AUTO RESTART)
[0]
OFF/Stop (OFF/STOP)
[1]
Function:
Setting of the desired operating mode when the mains
voltage is reconnected.
Description of choice:
Auto restart
[0] is selected if the frequency converter is
to start up in the same start/stop condition as immedi-
ately before power to the frequency converter is cut off.
OFF/Stop
[1] is selected if the frequency converter is
to remain stopped when the mains voltage is connec-
ted, until a start command is active. To restart, activate
the key [HAND START] or [AUTO START] by using
the control panel.
NB!
If [HAND START] or [AUTO START] can-
not be activated by the keys on the control
panel (see parameter 012/014
Hand/Auto
start on LCP)
the motor will not be able to
restart if
OFF/Stop
[1] is selected. If Hand-
start or Autostart has been programmed
for activation via the digital inputs, the mo-
tor will not be able to restart if
OFF/Stop
[1] is selected.
VLT
®
6000 HVAC Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
106
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark
Содержание VLT 6000 HVAC Series
Страница 31: ...Ordering form VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 31 Introduction to HVAC ...
Страница 63: ...Mechanical dimensions VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 63 Installation ...
Страница 75: ...VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 75 Installation ...
Страница 204: ...VLT 6000 HVAC Series 204 MG 61 B5 02 VLT is a registered Danfoss trademark ...