005
Max. value of user-defined readout
(CUSTOM READOUT)
Value:
0.01 - 999,999.99
100.00
Function:
This parameter allows a choice of the max. value of
the user-defined readout. The value is calculated on
the basis of the present motor frequency and the unit
selected in parameter 006
Unit for user-defined read-
out
. The programmed value is reached when the out-
put frequency in parameter 202
Output frequency high
limit
, f
MAX
is reached. The unit also decides whether
the ratio between output frequency and readout is lin-
ear, square or cubed.
Description of choice:
Set the required value for max. output frequency.
006
Unit for user-defined readout
(CUST. READ. UNIT)
No unit
1
[0]
GPM
1
[21]
%
1
[1]
gal/s
1
[22]
rpm
1
[2]
gal/min
1
[23]
ppm
1
[3]
gal/h
1
[24]
pulse/s
1
[4]
lb/s
1
[25]
l/s
1
[5]
lb/min
1
[26]
l/min
1
[6]
lb/h
1
[27]
l/h
1
[7]
CFM
1
[28]
kg/s
1
[8]
ft
3
/s
1
[29]
kg/min
1
[9]
ft
3
/min
1
[30]
kg/h
1
[10] ft
3
/h
1
[31]
m
3
/s
1
[11] ft
3
/min
1
[32]
m
3
/min
1
[12] ft/s
1
[33]
m
3
/h
1
[13] in wg
2
[34]
m/s
1
[14] ft wg
2
[35]
mbar
2
[15] PSI
2
[36]
bar
2
[16] lb/in
2
[37]
Pa
2
[17] HP
3
[38]
kPa
2
[18]
MWG
2
[19]
kW
3
[20]
Flow and speed units are marked with 1. Pressure
units with 2, and power units with 3. See figure in next
column.
Function:
Select a unit to be shown in the display in connection
with parameter 005
Max. value of user-defined readout
.
If units such as flow or speed units are selected, the
ratio between readout and output frequency will be a
linear one.
If pressure units are selected (bar, Pa, MWG, PSI,
etc.), the ratio will be square. If power units (HP, kW)
are selected, the ratio will be cubed.
The value and the unit are shown in display mode
whenever
User-defined readout
[10] has been selected
in one of parameters 007-010
Display readout
.
Description of choice:
Select the required unit for
User-defined readout
.
007
Large display readout
(LARGE READOUT)
Value:
Resulting reference [%] (REFERENCE [%])
[1]
Resulting reference [unit] (REFERENCE
[UNIT])
[2]
Frequency [Hz] (FREQUENCY [HZ])
[3]
% of maximum output frequency [%]
(FREQUENCY [%])
[4]
Motor current [A] (MOTOR CURRENT [A])
[5]
Power [kW] (POWER [KW])
[6]
Power [HP] (POWER [HP])
[7]
Output energy [kWh] (ENERGI [UNIT])
[8]
Hours run [Hours] (OURS RUN [h])
[9]
User-defined readout [-]
(CUSTOM READ.[UNITS]))
[10]
VLT
®
6000 HVAC Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
102
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark
Содержание VLT 6000 HVAC Series
Страница 31: ...Ordering form VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 31 Introduction to HVAC ...
Страница 63: ...Mechanical dimensions VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 63 Installation ...
Страница 75: ...VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 75 Installation ...
Страница 204: ...VLT 6000 HVAC Series 204 MG 61 B5 02 VLT is a registered Danfoss trademark ...