Mains supply 3 x 525-600 V
According to international requirements
VLT type
6152
6172
6222
6272
6352
6402
Output current
I
VLT,N
[A] (525-550 V)
162
201
253
303
360
418
I
VLT, MAX
(60 s) [A] (525-550
V)
178
221
278
333
396
460
I
VLT,N
[A] (551-600 V)
155
192
242
290
344
400
I
VLT, MAX
(60 s) [A] (551-600
V)
171
211
266
319
378
440
Output
S
VLT,N
[kVA] (550 V)
154
191
241
289
343
398
S
VLT,N
[kVA] (575 V)
154
191
241
289
343
398
Typical shaft output
[kW] (550 V)
110
132
160
200
250
315
[HP]
(575
V)
150
200
250
300
350
400
Max. cable cross-section to
motor
[mm
2
]
4,5
[AWG]
2,4,5
2 x 70
2 x 2/0
2 x 185
2 x 350 mcm
Max. cable cross-section to
loadsharing and brake
[mm
2
]
4,5
[AWG]
2,4,5
2 x 70
2 x 2/0
2 x 185
2 x 350 mcm
Rated input current
I
L,N
[A] (550 V)
158
198
245
299
355
408
I
L,N
[A] (575 V)
151
189
234
286
339
390
I
L,N
[A] (690 V)
155
197
240
296
352
400
Max. cable cross-section
power supply
[mm
2
]
4,5
[AWG]
2,4,5
2 x 70
2 x 2/0
2 x 185
2 x 350 mcm
Min. cable cross-section to
motor and power supply
[mm
2
]
4,5
[AWG]
2,4,5
35
2
Min. cable cross-section to
brake and loadsharing
[mm
2
]
4,5
[AWG]
2,4,5
10
8
Max. pre-fuses (mains) [-]/
UL
[A]
1
315
350
350
400
500
550
Efficiency
3
0,98
Power loss [W]
2963
3430
4051
4867
5493
5852
Weight
IP 00 [kg]
82
91
112
123
138
151
Weight
IP 21/Nema1 [kg]
96
104
125
136
151
165
Weight
IP 54/Nema12 [kg]
96
104
125
136
151
165
Enclosure
IP 00, IP 21/Nema 1 and IP 54/Nema12
1. For type of fuse see section
Fuses
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Max. cable cross-section is the maximum possible cable cross-section allowed to be fitted on the terminals. Min. cable cross-section is the minimum
allowed cross-section. Always comply with national and local regulations on min. cable cross-section.
5. Connection bolt 1 x M10 / 2 x M10 (mains and motor), connection bolt 1 x M8 / 2 x M8 (DC-bus).
VLT
®
6000 HVAC Series
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark
57
In
s
ta
lla
ti
on
Содержание VLT 6000 HVAC Series
Страница 31: ...Ordering form VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 31 Introduction to HVAC ...
Страница 63: ...Mechanical dimensions VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 63 Installation ...
Страница 75: ...VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 75 Installation ...
Страница 204: ...VLT 6000 HVAC Series 204 MG 61 B5 02 VLT is a registered Danfoss trademark ...