Function:
This parameter is used for setting the signal value that
has to correspond to the minimum reference or the
minimum feedback, parameter 204
Minimum refer-
ence, Ref
MIN
/413
Minimum feedback, FB
MIN
. See
Reference handling
or
Feedback handling
.
Description of choice:
Set the required voltage value.
For reasons of accuracy, voltage losses in long signal
lines can be compensated for.
If the time-out function is to be applied (parameters
317
Time out
and 318
Function after time out
), the value
must be set to > 1 V.
310
Terminal 53, max. scaling
(AI 53 SCALE HIGH)
Value:
0.0 - 10.0 V
10.0 V
Function:
This parameter is used for setting the signal value that
has to correspond to the maximum reference value or
the maximum feedback, parameter 205
Maximum ref-
erence, Ref
MAX
/414
Maximum feedback, FB
MAX
. See
Reference handling
or
Feedback handling
.
Description of choice:
Set the required voltage value.
For reasons of accuracy, voltage losses in long signal
lines can be compensated for.
311
Terminal 54, analog input voltage
(AI [V] 54 FUNCT.)
Value:
See description of parameter
308.
No operation
Function:
This parameter chooses between the different func-
tions available for the input, terminal 54.
Scaling of the input signal is done in parameter 312
Terminal 54, min. scaling
and in parameter 313
Termi-
nal 54, max. scaling
.
Description of choice:
See description of parameter 308.
For reasons of accuracy, voltage losses in long signal
lines should be compensated for.
312
Terminal 54, min. scaling
(AI 54 SCALE LOW)
Value:
0.0 - 10.0 V
0.0 V
Function:
This parameter is used for setting the signal value that
corresponds to the minimum reference value or the
minimum feedback, parameter 204
Minimum refer-
ence, Ref
MIN
/413
Minimum feedback, FB
MIN
. See
Reference handling
or
Feedback handling
.
Description of choice:
Set the required voltage value.
For reasons of accuracy, voltage losses in long signal
lines can be compensated for.
If the time-out function is to be applied (parameters
317
Time out
and 318
Function after time ou
t), the value
must be set to > 1 V.
313
Terminal 54, max. scaling
(AI 54 SCALE HIGH)
Value:
0.0 - 10.0 V
10.0 V
Function:
This parameter is used for setting the signal value that
corresponds to the maximum reference value or the
maximum feedback, parameter 205
Maximum refe-
rence, Ref
MAX
/414 Maximum feedback, FB
MAX
.
See
Reference handling
or
Feedback handling
.
Description of choice:
Set the required voltage value.
For reasons of accuracy, voltage losses in long signal
lines can be compensated for.
314
Terminal 60, analogue input current
(AI [mA] 60 FUNCT.)
Value:
See description of parameter 308.
Reference
Function:
This parameter allows a choice between the different
functions available for the input, terminal 60.
Scaling of the input signal is effected in parameter 315
Terminal 60, min. scaling
and in parameter 316
Termi-
nal 60, max. scaling
.
VLT
®
6000 HVAC Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark
129
Pr
ogr
a
mmi
ng
Содержание VLT 6000 HVAC Series
Страница 31: ...Ordering form VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 31 Introduction to HVAC ...
Страница 63: ...Mechanical dimensions VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 63 Installation ...
Страница 75: ...VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 75 Installation ...
Страница 204: ...VLT 6000 HVAC Series 204 MG 61 B5 02 VLT is a registered Danfoss trademark ...