Function:
This parameter sets up the drive’s Modbus RTU inter-
face to communicate properly with the master control-
ler. The parity (EVEN, ODD, or NO PARITY) must be
set to match the setting of the master controller.
Description of choice:
Select the parity that matches the setting for the Mod-
bus master controller. Even or odd parity is sometimes
used to allow a transmitted word to be checked for er-
rors. Because Modbus RTU uses the more efficient
CRC (Cyclic Redundancy Check) method of checking
for errors, parity checking is seldom used in Modbus
RTU networks.
571
Modbus communications timeout
(M.BUS COM.TIME.)
Value:
10 ms - 2000 ms
100 ms
Function:
This parameter determines the maximum amount of
time that the drive’s Modbus RTU will wait between
characters that are sent by the master controller.
When this amount of time expires, the drive’s Modbus
RTU interface will assume that it has received the en-
tire message.
Description of choice:
Generally, the value of 100 ms is sufficient for Modbus
RTU networks, although some Modbus RTU networks
may operate on a timeout value as short as 35 ms.
If this value is set too short, the drive’s Modbus RTU
interface may miss a part of the message. Since the
CRC check will not be valid, the drive will ignore the
message. The resulting retransmissions of messages
will slow communications on the network.
If this value is set too long, the drive will wait longer
than necessary to determine that the message is com-
pleted. This will delay the drive’s response to the mes-
sage and possibly cause the master controller to time
out. The resulting retransmissions of messages will
slow communications on the network.
VLT
®
6000 HVAC Series
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark
173
Pr
ogr
a
mmi
ng
Содержание VLT 6000 HVAC Series
Страница 31: ...Ordering form VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 31 Introduction to HVAC ...
Страница 63: ...Mechanical dimensions VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 63 Installation ...
Страница 75: ...VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 75 Installation ...
Страница 204: ...VLT 6000 HVAC Series 204 MG 61 B5 02 VLT is a registered Danfoss trademark ...