PNU
Parameter
Factory setting
Range
Change
s
4-Setup Conversion Data
#
description
during operation
index
type
100
Configuration
Open loop
No
Yes
0
5
101
Torque characteristics
Automatic Energy Optimi-
sation
No
Yes
0
5
102
Motor power, P
M,N
Depends on the unit
0.25-500 kW
No
Yes
1
6
103
Motor voltage, U
M,N
Depends on the unit
200-575 V
No
Yes
0
6
104
Motor frequency, f
M,N
50 Hz
24-1000 Hz
No
Yes
0
6
105
Motor current, l
M,N
Depends on the unit
0.01-I
VLT,MAX
No
Yes
-2
7
106
Rated motor speed, n
M,N
Depends on par. 102 Motor
power
100-60000 rpm
No
Yes
0
6
107
Automatic motor adaptation, AMA
Optimisation disable
No
No
0
5
108
Start voltage of parallel motors
Depends on par. 103
0.0 - par. 103
Yes
Yes
-1
6
109
Resonance dampening
100 %
0 - 500 %
Yes
Yes
0
6
110
High break-away torque
OFF
0.0 - 0.5 sec.
Yes
Yes
-1
5
111
Start delay
0.0 sec.
0.0 - 120.0 sec.
Yes
Yes
-1
6
112
Motor preheater
Disable
Yes
Yes
0
5
113
Motor preheater DC current
50 %
0 - 100 %
Yes
Yes
0
6
114
DC braking current
50 %
0 - 100 %
Yes
Yes
0
6
115
DC braking time
10 sec.
0.0 - 60.0 sec.
Yes
Yes
-1
6
116
DC brake cut-in frequency
OFF
0.0-par. 202
Yes
Yes
-1
6
117
Motor thermal proctection
ETR Trip 1
Yes
Yes
0
5
118
Motor power factor
0.75
0.50 - 0.99
No
Yes
-2
6
VLT
®
6000 HVAC Series
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark
211
A
ll
ab
out VL
T
60
00
HV
AC
Содержание VLT 6000 HVAC Series
Страница 31: ...Ordering form VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 31 Introduction to HVAC ...
Страница 63: ...Mechanical dimensions VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 63 Installation ...
Страница 75: ...VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 75 Installation ...
Страница 204: ...VLT 6000 HVAC Series 204 MG 61 B5 02 VLT is a registered Danfoss trademark ...