[Index 1-10]
Error Code: 0 - 99
Function:
This parameter makes it possible to see the reason
why a trip (cut-out of the frequency converter) occurs.
10 [1-10] log values are stored.
The lowest log number [1] contains the latest/most re-
cently saved data value; the highest log number [10]
contains the oldest data value.
If there is a trip on the frequency converter, it is pos-
sible to see its cause, the time and possibly the values
for output current or output voltage.
Description of choice:
Stated as an error code in which the number refers to
a table in
List of warnings and alarms
.
The fault log is only reset after manual initialization.
(See
Manual initialization
).
616
Fault log: Time
(F. LOG: TIME)
Value:
[Index 1-10]
Hours: 0 - 130,000.0
Function:
This parameter makes it possible to see the total num-
ber of hours run in connection with the 10 latest trips.
10 [1-10] log values are stored. The lowest log number
[1] contains the latest/most recently saved data value,
while the highest log number [10] contains the oldest
data value.
Description of choice:
The fault log is only reset after manual initialization.
(See
Manual initialization
).
617
Fault log: Value
(F. LOG: VALUE)
Value:
[Index 1 - 10]
Value: 0 - 9999
Function:
This parameter makes it possible to see the value at
which a trip occurred. The unit of the value depends
on the alarm active in parameter 615
Fault log: Error
code
.
Description of choice:
The fault log is only reset after manual initialization.
(
See Manual initialization
).
618
Reset of kWh counter
(RESET KWH COUNT)
Value:
No reset (DO NOT RESET)
[0]
Reset (RESET COUNTER)
[1]
Function:
Reset to zero of parameter 602
kWh counter.
Description of choice:
If Reset [1] has been selected and when the [OK] key
is pressed, the kWh counter of the frequency converter
is reset. This parameter cannot be selected via the se-
rial port, RS 485.
NB!
When the [OK] key has been activated,
the reset has been carried out.
619
Reset of hours-run counter
(RESET RUN. HOUR)
Value:
No reset (DO NOT RESET)
[0]
Reset (RESET COUNTER)
[1]
Function:
Reset to zero of parameter 601
Hours-run
.
Description of choice:
If Reset [1] has been selected and when the [OK] key
is pressed, parameter 601
Hours-run
is reset. This pa-
rameter cannot be selected via the serial port, RS 485.
NB!
When the [OK] key has been activated,
the reset has been carried out.
620
Operating mode
(OPERATION MODE)
Value:
Normal function (NORMAL OPERATION)
[0]
Function with de-activated inverter
(OPER. W/INVERT.DISAB)
[1]
Control card test (CONTROL CARD TEST)
[2]
Initialisation (INITIALIZE)
[3]
VLT
®
6000 HVAC Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
178
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark
Содержание VLT 6000 HVAC Series
Страница 31: ...Ordering form VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 31 Introduction to HVAC ...
Страница 63: ...Mechanical dimensions VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 63 Installation ...
Страница 75: ...VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 75 Installation ...
Страница 204: ...VLT 6000 HVAC Series 204 MG 61 B5 02 VLT is a registered Danfoss trademark ...