Immunity, continued
Burst
Surge
ESD
Radiated electro-
Mains
RF common
Radiated radio
Basic standard
IEC 1000-4-4
IEC 1000-4-5
1000-4-2
magnetic field
distortion
mode voltage
freq.elect.field
IEC 1000-4-3
VDE 0160
ENV 50141
ENV 50140
Acceptance criterion
B
B
B
A
A
A
Port connection
CM
DM
CM
-
-
CM
CM
Line
OK
OK
-
-
-
OK
OK
-
Motor
OK
-
-
-
-
-
OK
-
Control lines
OK
-
OK
-
-
-
OK
-
PROFIBUS option
OK
-
OK
-
-
-
OK
-
Signal Interface<3 m
OK
-
-
-
-
-
-
-
Enclosure
-
-
-
OK
OK
-
-
OK
Load sharing
OK
-
-
-
-
-
OK
-
Standard bus
OK
-
OK
-
-
-
OK
-
Basic specifications
-
-
-
-
Line
4 kV/5kHz/DCN
2 kV/2
Ω
4 kV/12
Ω
-
-
2,3 x U
N
2)
10 V
RMS
-
Motor
4 kV/5kHz/CCC
-
-
-
-
-
10 V
RMS
-
Control lines
2 kV/5kHz/CCC
-
2 kV/2
Ω
1)
-
-
-
10 V
RMS
-
PROFIBUS option
2 kV/5kHz/CCC
-
2 kV/2
Ω
1)
-
-
-
10 V
RMS
-
Signal interface<3 m
1 kV/5kHz/CCC
-
-
-
-
-
10 V
RMS
-
Enclosure
-
-
-
8 kV AD
6 kV CD
10 V/m
-
-
-
Load sharing
4 kV/5kHz/CCC
-
-
-
-
-
10 V
RMS
-
Standard bus
2 kV/5kHz/CCC
-
4 kV/2
1)
-
-
-
10 V
RMS
-
DM:
Differential mode
CM:
Common mode
CCC:
Capacitive clamp coupling
DCN:
Direct coupling network
1
)
Injection on cable shield
2
)
2.3 x U
N
: max. test pulse 380 V
AC
: Class 2/1250 V
PEAK
, 415 VAC: Class 1/1350 V
PEAK
VLT
®
6000 HVAC Series
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark
207
A
ll
ab
out VL
T
60
00
HV
AC
Содержание VLT 6000 HVAC Series
Страница 31: ...Ordering form VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 31 Introduction to HVAC ...
Страница 63: ...Mechanical dimensions VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 63 Installation ...
Страница 75: ...VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 75 Installation ...
Страница 204: ...VLT 6000 HVAC Series 204 MG 61 B5 02 VLT is a registered Danfoss trademark ...