LC filter VLT 6042-6062 200-240 V / VLT 6072-6552
380-460 V
The table and the drawing give the measurements of
IP 20 LC filters. IP 20 LC filters must be integrated and
protected against dust, water and aggressive gases.
Max. motor cable length:
- 150 m screened/armoured cable
- 300 m unscreened/unarmoured cable
If EMC standards are to be complied with:
- EN 55011-1B: Max. 50 m screened/armoured cable
Bookstyle: Max. 20 m screened/armoured cable
- EN 55011-1A: Max. 150 m screened/armoured ca-
ble
LC-filter IP 20
LC type
A [mm]
B [mm]
C [mm]
D [mm]
E [mm]
F [mm]
G [mm]
Weight [kg]
175Z4701
740
550
600
70
175Z4702
740
550
600
70
175Z4703
740
550
600
110
175Z4704
740
550
600
120
175Z4705
830
630
650
220
175Z4706
830
630
650
250
175Z4707
830
630
650
250
175Z3139
1350
800
1000
350
175Z3140
1350
800
1000
400
175Z3141
1350
800
1000
400
175Z3142
1350
800
1000
470
VLT
®
6000 HVAC Series
40
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark
Содержание VLT 6000 HVAC Series
Страница 31: ...Ordering form VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 31 Introduction to HVAC ...
Страница 63: ...Mechanical dimensions VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 63 Installation ...
Страница 75: ...VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 75 Installation ...