Sleep mode
Sleep mode makes it possible to stop the motor when
it is running at low speed, similar to a no load situation.
If consumption in the system goes back up, the fre-
quency converter will start the motor and supply the
power required.
NB!
Energy can be saved with this function,
since the motor is only in operation when
the system needs it.
Sleep mode is not active if
Local reference
or
Jog
has
been selected
The function is active in both
Open loop
and
Closed
loop
.
In parameter 403
Sleep mode timer
, the Sleep mode is
activated. In parameter 403
Sleep mode timer
, a timer
is set that determines how long the output frequency
can be lower than the frequency set in parameter 404
Sleep frequency
. When the timer runs out, the fre-
quency converter will ramp down the motor to stop via
parameter 207
Ramp-down time
. If the output frequen-
cy rises above the frequency set in parameter 404
Sleep frequency
, the timer is reset.
While the frequency converter has stopped the motor
in sleep mode, a theoretical output frequency is cal-
culated on the basis of the reference signal. When the
theoretical output frequency rises above the frequency
in parameter 405
Wake up frequency
, the frequency
converter will restart the motor and the output frequen-
cy will ramp up to the reference.
In systems with constant pressure regulation, it is ad-
vantageous to provide extra pressure to the system
before the frequency converter stops the motor. This
extends the time during which the frequency converter
has stopped the motor and helps to avoid frequent
starting and stopping of the motor, e.g. in the case of
system leaks.
If 25% more pressure is required before the frequency
converter stops the motor, parameter 406
Boost set-
point
is set to 125%.
Parameter 406
Boost setpoint
is only active in
Closed
loop
.
NB!
In highly dynamic pumping processes, it
is recommended to switch off the
Flying
Start
function (parameter 402).
VLT
®
6000 HVAC Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark
141
Pr
ogr
a
mmi
ng
Содержание VLT 6000 HVAC Series
Страница 31: ...Ordering form VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 31 Introduction to HVAC ...
Страница 63: ...Mechanical dimensions VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 63 Installation ...
Страница 75: ...VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 75 Installation ...
Страница 204: ...VLT 6000 HVAC Series 204 MG 61 B5 02 VLT is a registered Danfoss trademark ...