Single-pole start/stop
-
Start/stop using terminal 18.
Parameter 302 =
Start
[1]
-
Quick-stop using terminal 27.
Parameter 304 =
Coasting stop, inverse
[0]
Digital speed up/down
-
Speed up and down using terminals 32 and
33.
Parameter 306 =
Speed up
[7]
Parameter 307 =
Speed down
[7]
Parameter 305 =
Freeze reference
[2]
Potentiometer reference
-Parameter 308 =
Reference
[1]
Parameter 309 =
Terminal 53, min. scaling
Parameter 310 =
Terminal 53, max. scaling
Run permissive
-
Start permitted with terminal 16.
Parameter 300 =
Run permissive
[8]
-
Start/stop with terminal 18.
Parameter 302 =
Start
[1]
-
Quickstop with terminal 27.
Parameter 304 =
Coasting stop, inverse
[0].
-
Activated damper (motor)
Parameter 323 =
Start command active
[13].
2-zone regulation
-
Parameter 308 =
Feedback
[2].
-
Parameter 311 =
Feedback
[2].
Transmitter connection
-
Parameter 314 =
Reference
[1]
-
Parameter 315 =
Terminal 60, min. scaling
-
Parameter 316 =
Terminal 60, max. scaling
VLT
®
6000 HVAC Series
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark
91
In
s
ta
lla
ti
on
Содержание VLT 6000 HVAC Series
Страница 31: ...Ordering form VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 31 Introduction to HVAC ...
Страница 63: ...Mechanical dimensions VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 63 Installation ...
Страница 75: ...VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 75 Installation ...
Страница 204: ...VLT 6000 HVAC Series 204 MG 61 B5 02 VLT is a registered Danfoss trademark ...