556
Bus time interval function
(BUS TIME INTERVAL FUNCTION)
Value:
Off (OFF)
[0]
Freeze output (FREEZE OUTPUT)
[1]
Stop (STOP)
[2]
Jogging (JOG FREQUENCY)
[3]
Max. output frequency (MAX FREQUENCY)
[4]
Stop and trip (STOP AND TRIP)
[5]
Function:
In this parameter, the required reaction from the fre-
quency converter is selected when the time set in
parameter 555
Bus time interval
has been exceeded.
Description of choice:
The output frequency of the frequency converter can
be frozen at the present value at any given time, frozen
at parameter 211
Preset reference 1
, frozen at param-
eter 202
Max. output frequency
, or stop and activate
a cut-out.
560
N2 Override release time
(N2 OVER.REL.TIME)
Value:
1 - 65534 (OFF) sec.
OFF
Function:
In this parameter, the maximum time is set which is
expected to pass between the receipt of two N2 tele-
grams in a row. If this time is exceeded, the serial
communication is assumed to have stopped and all
points in the N2 point-map which are overridden will
be released in the order below:
1.
Release Analog Outputs from point address
(NPA) 0 to 255.
2.
Release Binary Outputs from point address
(NPA) 0 to 255.
3.
Release Internal Floating Points from point
address (NPA) 0 to 255.
4.
Release Internal Integer Points from point
address (NPA) 0 to 255.
5.
Release Internal Byte points from point ad-
dress (NPA) 0 to 255.
Description of choice:
Set the required time.
565
FLN Bus time interval
(FLN TIME INTER.)
Value:
1 - 65534 sec.
60 sec.
Function:
In this parameter, the maximum time is set which is
expected to pass between the receipt of two Apogee
FLN telegrams in a row. If this time is exceeded, the
serial communication is assumed to have stopped and
the required reaction is set in parameter 566
FLN Bus
time interval function
.
Description of choice:
Set the required time.
566
FLN Bus time interval function
(FLN TIME FUNCT)
Value:
Off (NO FUNCTION)
[0]
Freeze output (FREEZE OUTPUT)
[1]
Stop (STOP)
[2]
Jogging (JOG FREQUENCY)
[3]
Max. output frequency (MAX SPEED)
[4]
Stop and trip (STOP AND TRIP)
[5]
Function:
In this parameter, the required reaction from the fre-
quency converter is selected when the time set in
parameter 565
FLN Bus time interval
has been excee-
ded.
Description of choice:
The output frequency of the frequency converter can
be frozen at the present value at any given time, fro-
zen at parameter 211
Preset reference
1, frozen at
parameter 202
Max. output frequency
, or stop and ac-
tivate a cut-out.
570
Modbus parity and message framing
(M.BUS PAR./FRAME)
Value:
(EVEN/1 STOPBIT)
[0]
(ODD/1 STOPBIT)
[1]
(NO PARITY/1 STOPBIT)
[2]
(NO PARITY/2 STOPBIT)
[3]
VLT
®
6000 HVAC Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
172
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark
Содержание VLT 6000 HVAC Series
Страница 31: ...Ordering form VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 31 Introduction to HVAC ...
Страница 63: ...Mechanical dimensions VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 63 Installation ...
Страница 75: ...VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 75 Installation ...
Страница 204: ...VLT 6000 HVAC Series 204 MG 61 B5 02 VLT is a registered Danfoss trademark ...