Technical data, mains supply 3 x 200-240V
According to international requirements
VLT type 6002
6003
6004
6005
6006
6008
6011
Output current
4)
I
VLT,N
[A] 6.6
7.5
10.6
12.5
16.7
24.2
30.8
I
VLT, MAX
(60 s) [A] 7.3
8.3
11.7
13.8
18.4
26.6
33.9
Output power (240 V) S
VLT,N
[kVA]
2.7
3.1
4.4
5.2
6.9
10.1
12.8
Typical shaft output
P
VLT,N
[kW] 1.1
1.5
2.2
3.0
4.0
5.5
7.5
Typical shaft output
P
VLT,N
[HP] 1.5
2
3
4
5
7.5
10
Max. cable cross-sec-
tion to motor
and DC-bus
[mm
2
]/[AWG]
4/10
4/10
4/10
4/10
10/8
16/6
16/6
Max. input current
(200 V) (RMS)I
L,N
[A]
6.0
7.0
10.0
12.0
16.0
23.0
30.0
Max. cable
cross-section power
[mm
2
]/[AWG]
2 )
4/10
4/10
4/10
4/10
4/10
16/6
16/6
Max. pre-fuses
[-]/UL
1)
[A] 16/10
16/15
25/20
25/25
35/30
50
60
Efficiency
3)
0.95
0.95
0.95
0.95
0.95
0.95
0.95
Weight IP 20
[kg] 7
7
9
9
23
23
23
Weight IP 54
[kg]
11.5 11.5
13.5
13.5
35
35
38
Power loss at
max. load. [W]
Total 76
95
126
172
194
426
545
Enclosure
VLT type
IP 20 / IP 54
1. For type of fuse, see section
Fuses
.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Current ratings fulfill UL requirements for 208-240 V.
Technical data, mains supply 3x200-240V
According to international requirements
VLT type 6016
6022
6027
6032
6042
6052
6062
Output current
4)
I
VLT,N
[A]
(200-230 V)
46.2
59.4
74.8
88.0
115
143
170
I
VLT, MAX
(60 s)
[A] (200-230 V)
50.6
65.3
82.3
96.8
127
158
187
I
VLT,N
[A] (240 V)
46.0 59.4
74.8
88.0
104
130
154
I
VLT, MAX
(60 s)
[A] (240 V)
50.6 65.3
82.3
96.8
115
143
170
Output power
S
VLT,N
[kVA]
(240 V)
19.1
24.7
31.1
36.6
43.2
54
64
Typical shaft out-
put
P
VLT,N
[kW] 11
15
18.5
22
30
37
45
Typical shaft out-
put
P
VLT,N
[HP] 15
20
25
30
40
50
60
Max. cable cross-
section to motor
and DC-bus
[mm
2
]/[AWG]
2) 5)
Copper
Aluminium
6)
16/6
16/6
35/2
35/2
35/2
35/2
50/0
50/0
70/1/0
95/3/0
5)
95/3/0
90/250
mcm
5)
120/4/0
120/300
mcm
5)
Min. cable cross-section to motor
and DC-bus [mm
2
]/[AWG]
2)
10/8
10/8
10/8
16/6
10/8
10/8
10/8
Max. input current (200 V) (RMS)
I
L,N
[A]
46.0
59.2
74.8
88.0
101.3
126.6
149.9
Max. cable cross-
section power
[mm
2
]/[AWG]
2) 5)
Copper
Aluminium
6)
16/6
16/6
35/2
35/2
35/2
35/2
50/0
50/0
70/1/0
95/3/0
5)
95/3/0
90/250
mcm
5)
120/4/0
120/300
mcm
5)
Max. pre-fuses
[-]/UL
1)
[A]
60
80
125
125
150
200
250
Efficiency
3)
0.95
0.95
0.95
0.95
0.95
0.95
0.95
Weight IP 00
[kg]
- -
-
-
90
90
90
Weight IP 20/
NEMA 1
[kg] 23
30
30
48
101
101
101
Weight IP 54
[kg]
38 49
50
55
104
104
104
Power loss at
max. load.
[W] 545
783
1042
1243
1089
1361
1613
Enclosure
IP 00/IP 20/NEMA 1/IP 54
1. For type of fuse, see section
Fuses
.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Current ratings fulfill UL requirements for 208-240 V.
5. Connection stud 1 x M8 / 2 x M8.
6. Aluminium cables with cross section above 35 mm
2
must be connected by use of an Al-Cu connector.
VLT
®
6000 HVAC Series
48
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark
Содержание VLT 6000 HVAC Series
Страница 31: ...Ordering form VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 31 Introduction to HVAC ...
Страница 63: ...Mechanical dimensions VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 63 Installation ...
Страница 75: ...VLT 6000 HVAC Series MG 61 B5 02 VLT is a registered Danfoss trademark 75 Installation ...
Страница 204: ...VLT 6000 HVAC Series 204 MG 61 B5 02 VLT is a registered Danfoss trademark ...