2-01 DC Brake Current
Range:
Function:
50%
*
[0 - 1000 %]
Enter a value for current as a percentage of the rated motor current I
M,N
, see par. 1-24
Motor Current
. 100% DC
braking current corresponds to I
M,N
.
DC brake current is applied on a stop command, when the speed is lower than the limit set in par. 2-03
DC Brake
Cut In Speed
; when the DC Brake Inverse function is active; or via the serial communication port. The braking
current is active during the time period set in par. 2-02
DC Braking Time
.
NB!
The maximum value depends on the rated motor current.
NB!
Avoid 100 % current for too long. It may damage the motor.
2-02 DC Braking Time
Range:
Function:
10.0s.
*
[0.0 - 60.0 s.]
Set the duration of the DC braking current set in par. 2-01, once activated.
2-03 DC Brake Cut In Speed [RPM]
Range:
Function:
0 RPM
*
[0 - par. 4 -13]
Set the DC brake cut-in speed for activation of the DC braking current set in par. 2-01, upon a stop command.
2-04 DC Brake Cut In Speed [Hz]
Option:
Function:
[0 RPM]
*
0 - par. 4 -14
Set the DC brake cut-in speed for activation of the DC braking current set in par. 2-01, upon a stop command.
2.5.3. 2-1* Brake Energy Funct.
Parameter group for selecting dynamic braking parameters.
2-10 Brake Function
Option:
Function:
[0]
Off
No brake resistor is installed.
[1]
Resistor brake
A brake resistor is incorporated in the system, for dissipation of surplus brake energy as heat. Connecting a
brake resistor allows a higher DC link voltage during braking (generating operation). The Resistor brake function
is only active in frequency converters with an integral dynamic brake.
[2]
AC brake
2-11 Brake Resistor (ohm)
Range:
Function:
Size related [Ohm]
Set the brake resistor value in Ohms. This value is used for monitoring the power to the brake resistor in par.
2-13
Brake Power Monitoring
. This parameter is only active in frequency converters with an integral dynamic
brake.
2-12 Brake Power
Range:
Function:
kW
*
[0.001 - Size related]
Set the monitoring limit of the brake power transmitted to the resistor.
The monitoring limit is a product of the maximum duty cycle (120 sec.) and the maximum power of the brake
resistor at that duty cycle. See the formula below.