6-10 Terminal 53 Low Voltage
Range:
Function:
0.07 V
*
[FC 301: 0V - par. 6-11]
[FC 302: -10V - par. 6-11]
Enter the low voltage value. This analog input scaling value should correspond to the minimum reference value,
set in par. 6-14. See also the section
Reference Handling
.
6-11 Terminal 53 High Voltage
Range:
Function:
10.0V
*
[Par. 6-10 to 10.0 V]
Enter the high voltage value. This analog input scaling value should correspond to the high reference/feedback
value set in par. 6-15.
6-12 Terminal 53 Low Current
Range:
Function:
0.14 mA
*
[0.0 to par. 6-13 mA]
Enter the low current value. This reference signal should correspond to the minimum reference value, set in par.
3-02. The value must be set at >2 mA in order to activate the Live Zero Time-out Function in par. 6-01.
6-13 Terminal 53 High Current
Range:
Function:
20.0 mA
*
[ Par. 6-12 to 20.0 mA] Enter the high current value corresponding to the high reference/feedback set in par. 6-15.
6-14 Terminal 53 Low Ref./Feedb. Value
Range:
Function:
0.000 Unit
*
[-1000000.000 to par.
6-15]
Enter the analog input scaling value that corresponds to the low voltage/low current set in par. 6-10 and 6-12.
6-15 Terminal 53 High Ref./Feedb. Value
Range:
Function:
1500.000 Unit
*
[Par. 6-14 to
1000000.000]
Enter the analog input scaling value that corresponds to the maximum reference feedback value set in par. 6-11
and 6-13.
6-16 Terminal 53 Filter Time Constant
Range:
Function:
0.001s
*
[0.001 - 10.000 s]
Enter the time constant. This is a first-order digital low pass filter time constant for suppressing electrical noise
in terminal 53. A high time constant value improves dampening but also increases the time delay through the
filter.
This parameter cannot be adjusted while the motor is running.