9-65 Profile Number
Range:
Function:
Read only
0
*
[0 - 0]
This parameter contains the profile identification. Byte 1 contains the profile number and byte 2 the version
number of the profile.
NB!
This parameter is not visible via LCP.
9-67 Control Word 1
Range:
Function:
0
*
[0-65535]
This parameter accepts the Control Word from a Master Class 2 in the same format as PCD 1.
9-68 Status Word 1
Range:
Function:
0
*
[0-65535]
This parameter delivers the Status Word for a Master Class 2 in the same format as PCD 2.
9-70 Edit Set-up
Option:
Function:
Select the set-up to be edited.
[0]
Factory setup
Uses default data. This option can be used as a data source to return the other set-ups to a known state.
[1]
*
Setup 1
Edits Set-up 1.
[2]
Setup 2
Edits Set-up 2.
[3]
Setup 3
Edits Set-up 3.
[4]
Setup 4
Edits Set-up 4.
[9]
Active setup
Follows the active set-up selected in par. 0-10.
This parameter is unique to LCP and fieldbuses. See also par. 0-11
Edit set-up
.
9-71 Save Data Values
Option:
Function:
Parameter values changed via Profibus are not automatically stored in non-volatile memory. Use this parameter
to activate a function that stores parameter values in the EEPROM non-volatile memory, so changed parameter
values will be retained at power-down.
[0]
*
Off
Deactivates the non-volatile storage function.
[1]
Store edit setup
Stores all parameter values in the set-up selected in par. 9-70 in the non-volatile memory. The selection returns
to Off [0] when all values have been stored.
[2]
Store all set-ups
Stores all parameter values for all set-ups in the non-volatile memory. The selection returns to
Off
[0] when all
parameter values have been stored.
9-72 Drive Reset
Option:
Function:
[0]
*
No action
[1]
Power-on reset
Resets frequency converter upon power-up, as for power-cycle.
[3]
Comm. option reset
Resets the Profibus option only, useful after changing certain settings in parameter group 9-**, e.g. par. 9-18.
When reset, the frequency converter disappears from the fieldbus, which may cause a communication error
from the master.
FC 300 Programming Guide
2. How to Programme
MG.33.M3.02 - VLT
®
is a registered Danfoss trademark
117