![Danfoss FC 300 Скачать руководство пользователя страница 195](http://html1.mh-extra.com/html/danfoss/fc-300/fc-300_programming-manual_3466881195.webp)
No.
Description
Warning
Alarm/Trip
Alarm/Trip Lock
Parameter
Reference
61
Tracking Error
(X)
(X)
4-30
62
Output Frequency at Maximum Limit
X
63
Mechanical Brake Low
(X)
2-20
64
Voltage Limit
X
65
Control Board Over-temperature
X
X
X
66
Heat sink Temperature Low
X
67
Option Configuration has Changed
X
68
Safe Stop
(X)
(X)
1)
5-19
70
Illegal FC configuration
X
71
PTC 1 Safe Stop
X
X
1)
5-19
72
Dangerous Failure
X
1)
5-19
80
Drive Initialized to Default Value
X
90
Encoder Loss
(X)
(X)
17-61
91
Analogue input 54 wrong settings
X
S202
100-
199
See Operating Instructions for MCO 305
250
New spare part
X
14-23
251
New Type Code
X
X
Table 3.2: Alarm/Warning code list
(X) Dependent on parameter
1) Can not be Auto reset via Par 14-20
A trip is the action when an alarm has appeared. The trip will coast the
motor and can be reset by pressing the reset button or make a reset by
a digital input (Par. 5-1* [1]). The origin event that caused an alarm can-
not damage the frequency converter or cause dangerous conditions. A
trip lock is an action when an alarm occurs, which may cause damage to
frequency converter or connected parts. A Trip Lock situation can only be
reset by a power cycling.
LED indication
Warning
yellow
Alarm
flashing red
Trip locked
yellow and red
Alarm Word Extended Status Word
Bit
Hex
Dec
Alarm Word
Alarm Word 2
Warning Word
Warning
Word 2
Extended
Status Word
0
00000001
1
Brake Check
ServiceTrip, Read/
Write
Brake Check
Ramping
1
00000002
2
Pwr. Card Temp
ServiceTrip, (re-
served)
Pwr. Card Temp
AMA Running
2
00000004
4
Earth Fault
ServiceTrip, Type-
code/Sparepart
Earth Fault
Start CW/CCW
3
00000008
8
Ctrl.Card Temp
ServiceTrip, (re-
served)
Ctrl.Card Temp
Slow Down
4
00000010
16
Ctrl. Word TO
ServiceTrip,
(re-
served)
Ctrl. Word TO
Catch Up
5
00000020
32
Over Current
Over Current
Feedback High
6
00000040
64
Torque Limit
Torque Limit
Feedback Low
7
00000080
128
Motor Th Over
Motor Th Over
Output Current High
8
00000100
256
Motor ETR Over
Motor ETR Over
Output Current Low
9
00000200
512
Inverter Overld.
Inverter Overld.
Output Freq High
10
00000400
1024
DC under Volt
DC under Volt
Output Freq Low
11
00000800
2048
DC over Volt
DC over Volt
Brake Check OK
12
00001000
4096
Short Circuit
DC Voltage Low
Braking Max
13
00002000
8192
Inrush Fault
DC Voltage High
Braking
14
00004000
16384
Mains ph. Loss
Mains ph. Loss
Out of Speed Range
15
00008000
32768
AMA Not OK
No Motor
OVC Active
16
00010000
65536
Live Zero Error
Live Zero Error
AC Brake
17
00020000
131072
Internal Fault
KTY error
10V Low
KTY Warn
Password Timelock
18
00040000
262144
Brake Overload
Fans error
Brake Overload
Fans Warn
Password Protection
19
00080000
524288
U phase Loss
ECB error
Brake Resistor
ECB Warn
20
00100000
1048576
V phase Loss
Brake IGBT
21
00200000
2097152
W phase Loss
Speed Limit
22
00400000
4194304
Fieldbus Fault
Fieldbus Fault
Unused
23
00800000
8388608
24 V Supply Low
24V Supply Low
Unused
24
01000000
16777216
Mains Failure
Mains Failure
Unused
25
02000000
33554432
1.8V Supply Low
Current Limit
Unused
26
04000000
67108864
Brake Resistor
Low Temp
Unused
27
08000000
134217728
Brake IGBT
Voltage Limit
Unused
28
10000000
268435456
Option Change
Encoder loss
Unused
29
20000000
536870912
Drive Initialized
Output freq. lim.
Unused
30
40000000
1073741824
Safe Stop (A68)
PTC 1 Safe Stop
(A71)
Safe Stop (W68)
PTC 1 Safe
Stop (W71)
Unused
31
80000000
2147483648
Mech. brake low
Dangerous Failure
(A72)
Extended Status Word
Unused
Table 3.3: Description of Alarm Word, Warning Word and extended Status Word
FC 300 Programming Guide
3. Troubleshooting
MG.33.M3.02 - VLT
®
is a registered Danfoss trademark
195
3