[73]
SL Time-out 6
[74]
SL Time-out 7
Select the boolean input (TRUE or FALSE) to define the Smart Logic Controller event.See par. 13-01
Start Event
([0] - [61]) and par. 13-02
Stop Event
([70] - [74]) for further description.
13-52 SL Controller Action
Array [20]
[0]
*
Disabled
Select the action corresponding to the SLC event. Actions are executed when the corresponding event (defined
in par. 13-51) is evaluated as true. The following actions are available for selection:
*DISABLED
[0]
[1]
No action
No action
[1]
[2]
Select set-up 1
Select set-up 1
[2] - changes the active set-up (par. 0-10) to ‘1’.
[3]
Select set-up 2
Select set-up 2
[3] - changes the active set-up (par. 0-10) to ‘2’.
[4]
Select set-up 3
Select set-up 3
[4] - changes the active set-up (par. 0-10) to ‘3’.
[5]
Select set-up 4
Select set-up 4
[5] - changes the active set-up (par. 0-10) to ‘4’. If the set-up is changed, it will merge with
other set-up commands coming from either the digital inputs or via a fieldbus.
[10]
Select preset reference
0
Select preset reference 0
[10] – selects preset reference 0.
[11]
Select preset reference
1
Select preset reference 1
[11] – selects preset reference 1.
[12]
Select preset reference
2
Select preset reference 2
[12] – selects preset reference 2.
[13]
Select preset reference
3
Select preset reference 3
[13] – selects preset reference 3.
[14]
Select preset reference
4
Select preset reference 4
[14] – selects preset reference 4.
[15]
Select preset reference
5
Select preset reference 5
[15] – selects preset reference 5.
[16]
Select preset reference
6
Select preset reference 6
[16] – selects preset reference 6.
[17]
Select preset reference
7
Select preset reference 7
[17] - selects preset reference 7. If the active preset reference is changed, it will merge
with other preset reference commands coming from either the digital inputs or via a fieldbus.
[18]
Select ramp 1
Select ramp 1
[18] - selects ramp 1.
[19]
Select ramp 2
Select ramp 2
[19] - selects ramp 2.
[20]
Select ramp 3
Select ramp 3
[20] - selects ramp 3.
[21]
Select ramp 4
Select ramp 4
[21] - selects ramp 4.
[22]
Run
Run
[22] - issues a start command to the frequency converter.
[23]
Run reverse
Run reverse
[23] - issues a start reverse command to the frequency converter.
[24]
Stop
Stop
[24] - issues a stop command to the frequency converter.
[25]
Qstop
Qstop
[25] - issues a quick stop command to the frequency converter.
[26]
Dcstop
Dcstop
[26] - issues a DC stop command to the frequency converter.
[27]
Coast
Coast
[27] - the frequency converter coasts immediately. All stop commands including the coast command stop
the SLC.
[28]
Freeze output
Freeze output
[28] - freezes the output frequency of the frequency converter.
[29]
Start timer 0
Start timer 0
[29] - starts timer 0, see par. 13-20 for further description.
[30]
Start timer 1
Start timer 1
[30] - starts timer 1, see par. 13-20 for further description.
[31]
Start timer 2
Start timer 2
[31] - starts timer 2, see par. 13-20 for further description.
[32]
Set digital output A low
Set digital output A low
[32] - any output with SL output A will be low.
[33]
Set digital output B low
Set digital output B low
[33] - any output with SL output B will be low.
2. How to Programme
FC 300 Programming Guide
140