5-19 Terminal 37 Safe Stop
Option:
Function:
[1]
*
Safe Stop Alarm
Coasts frequency converter when safe stop is activated. Manual reset from LCP, digital input or fieldbus.
[3]
Safe Stop Auto Reset
Coasts frequency converter when safe stop is activated (term 37 off). When safe stop circuit is reestablished,
the frequency converter will continue without manual reset.
[4]
PTC 1 Alarm
Coasts frequency converter when safe stop is activated. Manual reset from LCP, digital input or fieldbus. Choice
4 is only available when the MCB 112 PTC Thermistor Card is connected.
[5]
PTC 1 Warning
Coasts frequency converter when safe stop is activated (term 37 off). When safe stop circuit is reestablished,
the frequency converter will continue without manual reset, unless a Digital Input set to PTC Card 1 [80] is still
enabled. Choice 5 is only available when the MCB 112 PTC Thermistor Card is connected.
[6]
PTC 1 & Relay A
This choice is used when the PTC option is gated together with a Stop button through a Safety relay to T-37.
Coasts frequency converter when safe stop is activated. Manual reset from LCP, digital input or fieldbus. Choice
6 is only available when the MCB 112 PTC Thermistor Card is connected.
[7]
PTC 1 & Relay W
This choice is used when the PTC option is gated together with a Stop button through a Safety relay to T-37.
Coasts frequency converter when safe stop is activated (term 37 off). When safe stop circuit is reestablished,
the frequency converter will continue without manual reset, unless a Digital Input set to PTC Card 1 [80] is (still)
enabled. Choice 7 is only available when the MCB 112 PTC Thermistor Card is connected.
[8]
PTC 1 & Relay A/W
This choice makes it possible to use a combination of Alarm and Warning. Choice 8 is only available when the
MCB 112 PTC Thermistor Card is connected.
[9]
PTC 1 & Relay W/A
This choice makes it possible to use a combination of Alarm and Warning. Choice 9 is only available when the
MCB 112 PTC Thermistor Card is connected.
NB!
When Auto Reset/ Warning is selected the frequency converter opens up for automatic restart.
Overview of functions, alarms and warnings
Function
No.
PTC
Relay
No Function
[0]
-
-
Safe Stop Alarm
[1]*
-
Safe Stop [A68]
Safe Stop Warning
[3]
-
Safe Stop [W68]
PTC 1 Alarm
[4]
PTC 1 Safe Stop [A71]
-
PTC 1 Warning
[5]
PTC 1 Safe Stop [W71]
-
PTC 1 & Relay A
[6]
PTC 1 Safe Stop [A71]
Safe Stop [A68]
PTC 1 & Relay W
[7]
PTC 1 Safe Stop [W71]
Safe Stop [W68]
PTC 1 & Relay A/W
[8]
PTC 1 Safe Stop [A71]
Safe Stop [W68]
PTC 1 & Relay W/A
[9]
PTC 1 Safe Stop [W71]
Safe Stop [A68]
W means warning and A means alarm. For further information, see Alarms and Warnings in section
Troubleshooting
in the Design Guide or the Operating
Instructions
A dangerous failure related to Safe Stop will give Alarm: Dangerous Fail-
ure [A72].
2.8.4. 5-3* Digital Outputs
Parameters for configuring the output functions for the output terminals. The 2 solid-state digital outputs are common for terminals 27 and 29. Set the
I/O function for terminal 27 in par. 5-01
Terminal 27 Mode
, and set the I/O function for terminal 29 in par. 5-02
Terminal 29 Mode
. These parameters
cannot be adjusted while the motor is running.
[0]
No operation
Default for all digital outputs and relay outputs
[1]
Control ready
The control board receives supply voltage.
[2]
Drive ready
The frequency converter is ready for operation and applies a supply signal on the control board.
FC 300 Programming Guide
2. How to Programme
MG.33.M3.02 - VLT
®
is a registered Danfoss trademark
85