Using a digital input and 10 V as power supply:
Example: The frequency converter trips when the motor temperature is too high.
Parameter set-up:
Set Par. 1-90
Motor Thermal Protection
to
Thermistor Trip
[2]
Set Par. 1-93
Thermistor Source
to
Digital Input
[6]
Using an analog input and 10 V as power supply:
Example: The frequency converter trips when the motor temperature is too high.
Parameter set-up:
Set Par. 1-90
Motor Thermal Protection
to
Thermistor Trip
[2]
Set Par. 1-93
Thermistor Source
to
Analog Input 54
[2]
Input
Digital/analog
Supply Voltage
Volt
Threshold
Cut-out Values
Digital
24 V
< 6.6 k
Ω
- > 10.8 k
Ω
Digital
10 V
< 800
Ω
- > 2.7 k
Ω
Analog
10 V
< 3.0 k
Ω
- > 3.0 k
Ω