1-20 Motor Power
Range:
Function:
Size related
*
[0.09 - 1200 kW]
Enter the nominal motor power in kW according to the motor nameplate data. The default value corresponds to
the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running. This parameter is visible in LCP if par. 0-03 is
International
[0].
NB!
Four sizes down, one size up from nominal VLT rating.
1-21 Motor Power [HP]
Range:
Function:
Size related
*
[0.09 - 500 HP]
Enter the nominal motor power in HP according to the motor nameplate data. The default value corresponds to
the nominal rated output of the unit. This parameter is visible in LCP if par. 0-03 is
US
[1]
1-22 Motor Voltage
Range:
Function:
Size related
*
[10 - 1000 V]
Enter the nominal motor voltage according to the motor nameplate data. The default value corresponds to the
nominal rated output of the unit.
1-23 Motor Frequency
Option:
Function:
Min - Max motor frequency: 20 - 1000 Hz.
Select the motor frequency value from the motor nameplate data. If a value different from 50 Hz or 60 Hz is
selected, it is necessary to adapt the load independent settings in par. 1-50 to 1-53. For 87 Hz operation with
230/400 V motors, set the nameplate data for 230 V/50 Hz. Adapt par. 4-13
Motor Speed High Limit [RPM)
and
par. 3-03
Maximum Reference
to the 87 Hz application.
[50]
*
50 Hz when parameter
0-03 = international
[60]
60 Hz when parameter
0-03 = US
1-24 Motor Current
Option:
Function:
[Motor type
dependent.]
Enter the nominal motor current value from the motor nameplate data. The data are used for calculating torque,
motor protection etc.
1-25 Motor Nominal Speed
Range:
Function:
Size related
*
[10 - 60000 RPM]
Enter the nominal motor speed value from the motor nameplate data. The data are used for calculating motor
compensations.
1-26 Motor Cont. Rated Torque
Range:
Function:
Size related [1.0 - 10000.0 Nm]
Enter the value from the motor nameplate data. The default value corresponds to the nominal rated output. This
parameter is available when par. 1-10
Motor Construction
is set to
PM, non salient SPM
[1], i.e. the parameter is
valid for PM and non-salient SPM motors only.