![Danfoss FC 300 Скачать руководство пользователя страница 160](http://html1.mh-extra.com/html/danfoss/fc-300/fc-300_programming-manual_3466881160.webp)
16-40 Logging Buffer Full
View whether the logging buffer is full (see par. 15-1*). The logging buffer will never be full when
par. 15-13 Logging
Mode
is set to
Log always
[0].
[0]
*
No
[1]
Yes
2.17.5. 16-5* Ref. & Feedb.
Parameters for reporting the reference and feedback input.
16-50 External Reference
Range:
Function:
0.0
*
[-200.0 - 200.0]
View the total reference, the sum of digital, analog, preset, bus and freeze references, plus catch-up and slow-
down.
16-51 Pulse Reference
Range:
Function:
0.0
*
[-200 - 200]
View the reference value from programmed digital input(s). The read-out can also reflect the impulses from an
incremental encoder.
16-52 Feedback [Unit]
Range:
Function:
0.0
*
[-999999.999 - 999999.999] View the feedback unit resulting from the selection of unit and scaling in par. 3-00, 3-01, 3-02 and 3-03.
16-53 Digi Pot Reference
Range:
Function:
0.0
*
[-200 - 200]
View the contribution of the Digital Potentiometer to the actual reference.
2.17.6. 16-6* Inputs and Outputs
Parameters for reporting the digital and analog IO ports.
16-60 Digital Input
Range:
Function:
0
*
[0 - 63]
View the signal states from the active digital inputs. Example: Input 18 corresponds to bit no. 5, ‘0’ = no signal,
‘1’ = connected signal. Bit 6 works in the opposite way, on = '0', off = '1' (safe stop input).
Bit 0
Digital input term. 33
Bit 1
Digital input term. 32
Bit 2
Digital input term. 29
Bit 3
Digital input term. 27
Bit 4
Digital input term. 19
Bit 5
Digital input term. 18
Bit 6
Digital input term. 37
Bit 7
Digital input GP I/O term. X30/4
Bit 8
Digital input GP I/O term. X30/3
Bit 9
Digital input GP I/O term. X30/2
Bit 10-63
Reserved for future terminals
16-61 Terminal 53 Switch Setting
View the setting of input terminal 53. Current = 0; Voltage = 1.
[0]
*