8-32 FC Port Baud Rate
Option:
Function:
[0]
2400 Baud
[1]
4800 Baud
[2]
*
9600 Baud
[3]
19200 Baud
[4]
38400 Baud
[7]
115200 Baud
Baud rate selection for the FC (standard) port.
8-35 Minimum Response Delay
Range:
Function:
10ms
*
[1 - 500 ms]
Specify the minimum delay time between receiving a request and transmitting a response. This is used for over-
coming modem turnaround delays.
8-36 Max Response DelayMax Response Delay
Range:
Function:
5000ms
*
[1 - 10000 ms]
Specify the maximum permissible delay time between transmitting a request and receiving a response. Exceeding
this delay time will cause control word time-out.
8-37 Max Inter-Char Delay
Range:
Function:
25ms
*
[0 - 30 ms]
Specify the maximum permissible time interval between receipt of two bytes. This parameter activates time-out
if transmission is interrupted.
This parameter is active only when par. 8-30 is set to
FC MC
[1] protocol.
8-40 FC MC Protocol Set
Option:
Function:
[1]
*
Standard Telegram 1
[200]
Custom Telegram
Enables use of freely configurable telegrams or standard telegrams for the FC port.
2.11.5. 8-5* Digital/Bus
Parameters for configuring the control word Digital/Bus merging.
8-50 Coasting Select
Select control of the coasting function via the terminals (digital input) and/or via the bus.
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3]
*
Logic OR
NB!
This parameter is active only when
par. 8-01 Control Site
is set to [0]
Digital and control word
.
8-51 Quick Stop Select
Option:
Function:
[0]
Digital input
[1]
Bus
[2]
Logic AND